| Plan Review Notes For Permit 02041045 |
| Permit Number |
02041045 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-04-22 00:00:00 | | | | 1.PROVIDE MANUFACTURER SUBMITTAL FOR | | | THE 3M FASTWRAP+. | | | | | | 2.INDICATE 1 OR 2 HR RATING. | | | | | | 3.AS PER 2001 FBC, MECHANICAL 306.5, | | | EQUIPMENT & APPLIANCES REQUIRING | | | ACCESS ARE INSTALLED ON ROOFS OR | | | ELEVATED STRUCTURES AT A HEIGHT | | | EXCEEDING 16 FT, SUCH ACCESS SHALL | | | BE PROVIDED BY A PERMANENT APPROVED | | | MEANS OF ACCESS. | | | | | | 4.WHERE APPLIANCES ARE INSTALLED ON A | | | ROOF HAVING A SLOPE OF 3 UNITS | | | VERTICAL IN 12 UNIT HORIZONTAL OR | | | GREATER, A LEVEL PLATFORM SHALL BE | | | PROVIDED ON EACH SIDE OF THE | | | APPLIANCE TO WHICH ACCESS IS | | | REQUIRED.2001 FBC(M) 306.6. | | | | | | 5.AS PER NFPA 96 4-8.2.1 (A), A MIN. | | | OF 10 FT SEPARATION FROM THE OUTLET | | | TO ADJACENT BUILDINGS, PROPERTY | | | LINES, AND AIR INTAKES. | | | | | | 6.SHOW COMPLIANCE WITH 2001 FBC(M) | | | 508.1.1, THE TEMPERATURE | | | DIFFERENTIAL BETWEEN THE MAKEUP AIR | | | AND THE AIR IN THE CONDITIONED SPACE | | | SHALL NOT EXCEED 10 DEGREES. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|