Plan Review Notes
Plan Review Notes For Permit 02041045
Permit Number 02041045
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2002-05-02 00:00:001) PLANS MAKE REFERENCE TO HOOD WRAPPING
 BUT NO DOCUMENTATION WAS SUBMITTED WITH
 PLANS.
 2) PLEASE INDICATE ON THE PLANS THAT
 THE MAKE-UP AIR IS A MINIMUM OF 10 FEET
 FROM THE HOOD EXHAUST.
 3) GREASE EXHAUST DUCT IS TO BE A
 MINIMUM OF AT LEAST 10 FEET FROM
 ADJACENT BUILDING, PROPERTY LINES,
 ETC.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910