| Plan Review Notes For Permit 02041045 |
| Permit Number |
02041045 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-05-02 00:00:00 | 1) PLANS MAKE REFERENCE TO HOOD WRAPPING | | | BUT NO DOCUMENTATION WAS SUBMITTED WITH | | | PLANS. | | | 2) PLEASE INDICATE ON THE PLANS THAT | | | THE MAKE-UP AIR IS A MINIMUM OF 10 FEET | | | FROM THE HOOD EXHAUST. | | | 3) GREASE EXHAUST DUCT IS TO BE A | | | MINIMUM OF AT LEAST 10 FEET FROM | | | ADJACENT BUILDING, PROPERTY LINES, | | | ETC. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|