| Plan Review Notes For Permit 02040979 |
| Permit Number |
02040979 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-04-27 00:00:00 | DENIED; | | | 1.PLUMBING RISER DIAGRAM. MASTER BATH | | | NO MORE THAN 4 FIXTURE UNITS PERMITED | | | ON A 2" WET VENT. SIZE OF PIPE TO BE | | | 3" AFTER TUB. TABLE 909.3. | | | NOTES; | | | NOTE #3 MINIMUM SLOPE OF PIPE TO COMPLY | | | WITH TABLE 704.1. PIPE LESS THAN | | | 3" SHALL SLOPE AT 1/4". | | | NOTE#5 NO FLOOR DRAINS SHOWN ON DRAWING. | | | NOTE NOT NEEDED. | | | NOTE#6 CONDENSATE IS NOT PERMITED TO | | | DUMP INTO SANITARY SEWER SYSTEM | | | CITY UTILITY'S REQUIREMENT. | | | NOTE#7 WATER HAMMER ARRESTORS ARE | | | REQUIRED. SEE SEC. 604.9 FOR | | | LOCATIONS REQUIRED. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT. 8369 |
|