| 2002-05-08 00:00:00 | ***************** UNSAT ************* |
| | |
| | 1) NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| | DWELLING UNIT. ROOMS WITH BATHS AND OR |
| | CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| | PER NFPA-72 2-2.1.1.1. |
| | IN THE VICINITY OF BEDROOMS AND CLOSE |
| | PROXIMITY OF STIRWAYS. 2-5.2.1.3 |
| | 3'FT FROM BATHS/KITCHENS.2-5.2.1.6 |
| | PLEASE NOTE MISSING FROM DOWNSTAIRS |
| | BEDROOM. |
| | |
| | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | |
| | 3) NOTE: PLEASE SHOW ALL OUTLET SPACING |
| | TO MEET 2`,6`,12` RULE PER 210-52. |
| | MISSING UPSTAIRS BED RM. |
| | |
| | 4)NOTE: PLEASE NOTE MISSING OUTLET FOR |
| | A/C EQUIPMENT. PER 210-63 AND/OR SECTION |
| | 306 OF THE MECHANICAL CODE. |
| | |
| | 6) NOTE: PLEASE SHOW GROUNDING ELECTRODE |
| | GOING TO BUILDING STEEL AND COLD WATER |
| | PER 250-50. SIZE PER 250-66 |
| | |
| | 7))NOTE: PLEASE CLARIFY EQUIPMENT |
| | GROUNDING METHOD BETWEEN FIRST MEANS |
| | OF DISCONNECT AND PANELS. PLEASE SIZE |
| | CONDUCTORS PER 250-122. |
| | |
| | 8)NOTE: PLEASE NOTE THAT PER LOCAL |
| | AMENDMENTS ALL SERVICE ENTRANCE CONDUCT- |
| | ORS SHALL BE IN A RACEWAY SPECIFIED IN |
| | 230-43. |
| | PLEASE ALSO NOTE THAT NO ALUM CONDUCTORS |
| | MAY BE USED SMALLER THAN #2. 310-2 |
| | AND NO ALUM FOR GROUNDING/OR BONDING. |
| | 310-2B 1&2 |
| | |
| | 9)NOTE: PLEASE NOTE MISSING A/C DISC`S |
| | FOR AHU`S PER 440-11 |
| | |
| | |
| | |
| | |
| | |
| | |
| | 11)NOTE: PLEASE NOTE,ELECTRICAL NOTE |
| | ON PLANS MENTIONS TO PLACE SD`S ON BATH |
| | AND KITCHEN CIRCUIT? PLEASE CLARIFY |
| | LIGHTING CIRCUIT??? 210-11-C1/210-11C-3 |
| | |
| | 12)NOTE: PLEASE LIST THE REQ`D ARC FAULT |
| | PROTECTED CIRCUITS PER 210-12 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |