| 2002-05-08 00:00:00 | ******************* UNSAT ************* |
| | |
| | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | |
| | 2) NOTE: PLEASE SHOW GROUNDING ELECTRODE |
| | GOING TO BUILDING STEEL AND COLD WATER |
| | PER 250-50. SIZE PER 250-66 |
| | |
| | 3)NOTE: PLEASE NOTE MISSING OUTLET FOR |
| | A/C EQUIPMENT. PER 210-63 AND/OR SECTION |
| | 306 OF THE MECHANICAL CODE. |
| | |
| | 4))NOTE: PLEASE CLARIFY EQUIPMENT |
| | GROUNDING METHOD BETWEEN FIRST MEANS |
| | OF DISCONNECT AND PANELS. PLEASE SIZE |
| | CONDUCTORS PER 250-122. |
| | |
| | 5) NOTE: PLEASE SHOW ALL OUTLET SPACING |
| | TO MEET 2`,6`,12` RULE PER 210-52. |
| | 210-52H HALLWAY MASTER BR. |
| | |
| | 6)) NOTE: PLEASE NOTE FRONT AND REAR |
| | RECEPTS REQ`D PER 210-52E |
| | MISSING REAR. |
| | |
| | 7 )NOTE: PLEASE LIST THE REQ`D ARC |
| | FAULT PROTECTED CIRCUITS ON PANEL |
| | SCHEDULE. PER 210-12 |
| | |
| | 8)NOTE: PLEASE NOTE THAT PER LOCAL |
| | AMENDMENTS, ALL SERVICE ENTRANCE |
| | CONDUCTORS AND FEEDER TO PANELS SHALL |
| | BE IN A RACEWAY.230-43 OF THE LOCAL |
| | CODE. PLEASE NOTE NO ALUM CONDUCTORS OF |
| | ANY KIND SMALLER THAN #2 IS PERMITTED. |
| | PLEASE ASLO NOTE THAT NO ALUM CONDUCTORS |
| | CAN BE USED FOR GROUNDING OR BONDING. |
| | 310-2 |
| | |
| | 9)NOTE: PLEASE NOTE THAT ELECTRRICAL |
| | NOTES MENTION, SD`S TO COME FROM BATH |
| | AND KITCHEN CIRCUITS? PLEASE CLARIFY? |
| | LIGHTING? PLEASE NOTE 210-11-C1/C1 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMAITON FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |