| Date |
Text |
| 2002-05-08 00:00:00 | ****************** UNSAT ************* |
| | |
| | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | |
| | 2) NOTE: PLEASE SHOW GROUNDING ELECTRODE |
| | GOING TO BUILDING STEEL AND COLD WATER |
| | PER 250-50. SIZE PER 250-66 |
| | |
| | 3) NOTE: PLEASE SHOW ALL OUTLET SPACING |
| | TO MEET 2`,6`,12` RULE PER 210-52. |
| | MISSING BED RM |
| | |
| | 4)NOTE: PLEASE NOTE MISSING OUTLET FOR |
| | A/C EQUIPMENT. PER 210-63 AND/OR SECTION |
| | 306 OF THE MECHANICAL CODE. |
| | |
| | 5))NOTE: PLEASE LIST THE REQ`D ARC |
| | FAULT PROTECTED CIRCUITS ON PANEL |
| | SCHEDULE. PER 210-12 |
| | |
| | 6)NOTE: PLEASE NOTE THAT PER LOCAL |
| | AMENDMENTS , ALL SERVICE ENTRANCE |
| | CONDUCTORS SHALL BE IN A RACEWAY AS |
| | SPECIFIED IN 230-43 OF THE LOCAL CODE. |
| | PLEASE ALSO NOTE NO ALUM CONDUCTORS OF |
| | ANY KIND SMALLER THAN #2 AND NONE FOR |
| | GROUNDING OR BONDING. 310-2 |
| | |
| | 7)NOTE: PLEASE NOTE THAT ELECTRICAL |
| | NOTES MENTIONS TO PLACE SD`S ON KITCHEN |
| | AND BATH CIRCUITS? PLEASE CLARIFY. |
| | LIGHTING? |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |