| Plan Review Notes For Permit 02040876 |
| Permit Number |
02040876 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-05-11 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1) SHT A-0.1 APPLICABLE CODE ARE NOT | | | STANTARD CODES BUT FLA. BLDG. CODES. | | | PLEASE CHANGE REFERENCE. | | | 2) SHT A-2.2 DRINKING FOUNTAIN, EITHER | | | HI-LOW DRINKING FOUNTAIN OR OTHER PROVI- | | | SIONS FOR THOSE WHO HAVE DIFFICULTY | | | BENDING OR STOOPING PER FBC 11-4.1.3(10) | | | 3) SHT P-1 WATER RISER DIAGRAM, AIR | | | CHAMBERS NOT APPROVED. WATER HAMMER ARR- | | | ESTORS ARE REQUIRED FOR QUICK CLOSING | | | VALVES (DISHWASHERS, ICE MAKERS, WASH | | | MACHINES ECT). IF USED THEY SHALL BE LO- | | | CATED NEAR THE FIXTURE IN AN "EFFECTIVE | | | RANGE" NOT AT TOP OF DROPS AS SHOWN. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|