2002-04-29 00:00:00*************** UNSAT *****************
  
 1 )NOTE: PLEASE NOTE THAT THE LOAD
 CALCULATIONS NEED TO BE SHOWN. SQ FT/
 RECEPT LOADS ETC. PER 220-3,220-10,
 220-11, 220-13. (215-5)
 PLEASE NOTE THAT ALL CONTINUOUS LOADS
 NEED TO BE SHOWN AT 125%. 230-42/215-2,3
  
  
 2)NOTE: PLEASE NOTE THAT WE ARE UNDER
 THE "99" NEC. PLEASE NOTE TAHT PLANS
 SHOW 1997? PLEASE ALSO NOTE THAT PLANS
 SHOW WRONG CODES FOR OTHER TRADES.
 PLEASE SEE COMMENTS FROM OTHER REVIEWERS
  
 3)NOTE: PLEASE NOTE TWO " 1TC" PANELS
 SHOWN ON MDP. (MISPRINT)
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANYQUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 5661-659-8096 EXT 8372