| Plan Review Notes For Permit 02040876 |
| Permit Number |
02040876 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-04-29 00:00:00 | *************** UNSAT ***************** | | | | | | 1 )NOTE: PLEASE NOTE THAT THE LOAD | | | CALCULATIONS NEED TO BE SHOWN. SQ FT/ | | | RECEPT LOADS ETC. PER 220-3,220-10, | | | 220-11, 220-13. (215-5) | | | PLEASE NOTE THAT ALL CONTINUOUS LOADS | | | NEED TO BE SHOWN AT 125%. 230-42/215-2,3 | | | | | | | | | 2)NOTE: PLEASE NOTE THAT WE ARE UNDER | | | THE "99" NEC. PLEASE NOTE TAHT PLANS | | | SHOW 1997? PLEASE ALSO NOTE THAT PLANS | | | SHOW WRONG CODES FOR OTHER TRADES. | | | PLEASE SEE COMMENTS FROM OTHER REVIEWERS | | | | | | 3)NOTE: PLEASE NOTE TWO " 1TC" PANELS | | | SHOWN ON MDP. (MISPRINT) | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANYQUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 5661-659-8096 EXT 8372 |
|