2002-05-14 00:00:00BUILDING PLAN REVIEW
 PERMIT # 02040734
 3408 WASHINGTON RD
 CONT: BURKHARDT CONST
 TEL: 659-1400
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) THE FINISHED FLOOR LEVEL SHALL BE
 VERIFIED BY A SIGNED AND SEALED
 ELEVATION CERTIFICATE. THIS STRUCTURE
 IS LOCATEDIN A A-5 FLOOD ZONE. THE CITY
 CODE 12-22(1) REQUIRES SUBSTANTIAL IMPRO
 VEMENTS TO BE 6" ABOVE THE BASE FLOOD
 ELEVATION, OR A FINISH FLOOR HEIGTH OF
 7'-6". THE ADDITION SHALL COMPLY WITH
 THIS REQUIREMENT.
 NOTE: ANY POOL OR A/C EQUIPMENT (ELEC)
 SHALL HAVE THE MINIMUM FINISH SLAB
 HEIGTH OF 7'-6".
  
 2)PLANS SUBMITTED AFTER FEB. 28/2002
 SHALL BE DESIGNED TO THE 2001 FLORIDA
 BUILDING CODE. S-201 INDICATES THAT THE
 PLANS WERE DESIGNED UNDER THE 2001 STAND
 ARD BUILDING CODE @ 110 MPH.
  
 3)FIGURE 1606 WIND-BORNE DEBRIS
 REGION; INDICATES THAT W.P.B. CITY OF IS
 LOCATED IN THE 140 MPH ZONE. PLANS ARE
 TO INDICATE THIS.
  
 4)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 5)FL BLDG 1909.3 (EXEPTION# 2)
 CONCRETE SLABS ON GRADE CONTAINING 6X6/
 W1.4XW1.4 WELDED WIRE REINFORCEMENT
 FABRIC LOCATED IN THE MIDDLE TO THE
 UPPER 1/3RD OF THE SLAB SHALL BE SUP-
 PORTED BY APPROVED MATERIALS OR SUPPORTS
 AT SPACING NOT TO EXCEED 3 FT OR IN
 ACCORDANCE WITH MANUFACTURER'S SPEC.
  
 5) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED.
 WINDOWS SHALL REQUIRE STORM SHUTTERS
 SINCE WINDOW TESTING IS ONLY FOR WIND.
 ROOFING REPORT FOR SHINGLES SHALL ALSO
 BE REQUIRED.
  
 6)1012.5 GROUP R-3 LANDING WIDTH SHALL
 BE NO LESS THAN THE DOOR WIDTH IT SERVES
 AND THE DEPTH SHALL BE NO LESS THAN 36"
 THE LANDING MAY BE ONE STEP LOWER THAN
 THE INSIDE FLOOR LEVEL BUT NOT MORE THAN
 7" LOWER.
  
 7) 1803.1.3 EXCAVATIONS FOR ANY PURPOSE
 SHALL NOT EXTEND WITHIN 1 FT OF THE
 ANGLE OF REPOSE OR NATURAL SLOPE OF SOIL
 UNDER ANY FOOTING OR FOUNDATION, UNLESS
 SUCH FOOTINGS OR FOUNDATION IS FIRST
 PROPERLY UNDERPINNED OR PROTECTED
 AGAINST SETTLEMENT. IF THE ADDITION IS
 STARTED BEFORE THE POOL THIS CONDITION
 SHALL OCCUR.
  
 8) A-701 NOR S-202 GIVE HOW OFTEN THE
 GABLE END TRUSS SHOULD BE ANCHORED?
  
 9) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 ANY QUESTIONS PLEASE CALL,
 JIM WITMER
 BUILDING PLAN REVIEW
 DEPARTMENT OF CONSTRUCTION SERVICES
 CITY OF WEST PALM BEACH
 (561) 659-8096 EXT. 8412