| Plan Review Notes For Permit 02040724 |
| Permit Number |
02040724 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-04-24 00:00:00 | DENIED | | | REFERENCE: FBC-2001 424.2 SWIMMING POOLS | | | | | | 1) PLEASE ADJUST YOUR NOTES, DETAILS, OR | | | SUBMITTALS TO REFLECT THE FOLLOWING IN- | | | FORMATION REQUIRED FOR PLAN REVIEW | | | A) | | | FBC-2001 SEC 424.2.6.1 ENGINEERING | | | DESIGN, CONSTRUCTION AND WORKMANSHIP. | | | ANSI/NSPI-4 92.(SEE NOTE #10) | | | B) | | | FBC-2001 SEC 424.2.6.6.2 SHOW COMPLIANCE | | | WITH ANSI/ASME A112.19.8M. PROVIDE MODEL | | | NUMBER AND MANUF INFO FOR VAC LOCK. | | | (GIVE DETAIL OR ADD NOTE)(SUBMITTAL) | | | C) | | | FBC-2001 SEC 424.2.6.6.5 WHERE PROVIDED, | | | THE VACUUM OR PRESSURE CLEANER FITTING | | | SHALL BE LOCATED AT LEAST 6" AND NOT | | | GREATER THAN 12" BELOW THE MINIMUM OPER- | | | ATING WATER LEVEL OR AS AN ATTACHMENT TO | | | THE SKIMMER. | | | D) | | | FBC-2001 SEC 424.2.12.1 PRESSURE TESTS. | | | PER MANUFACTURE RECOMMENDATIONS, NO AIR | | | TEST SHALL BE APPROVED FOR PVC PIPE AND | | | FITTINGS. (ADD TO NOTES) | | | | | | 2) ALL REFERENCES TO SFBC, (SEE PAGE 3), | | | SHALL BE DELETED. PRESENT CODE IS FBC- | | | 2001 | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|