| Plan Review Notes For Permit 02040697 |
| Permit Number |
02040697 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-04-29 00:00:00 | ****************** UNSAT ************** | | | | | | 1)NOTE:PLEASE NOTE THAT ALL BRANCH | | | CIRCUIT #`S ARE TO BE ON PLANS AND TO | | | CORRELATE WITH A SUBMITTED PANEL | | | SCHEDULE. | | | | | | 2)NOTE: PLEASE NOTE LOAD CALCULATIONS | | | NEED TO BE SUBMITTED FOR ALL NEW LOADS | | | ADDED. 220 OF THE NEC. 215-5,220-3,220- | | | -10,220-11,220-13. PLEASE NOTE ALL | | | CONTINUOUS LOAD AT 125%. 215-2-3, 230-42 | | | | | | | | | 3)NOTE: PLEASE NOTE THAT A CONTRACT | | | NEEDS TO BE SUBMITTED TO VERIFY VALUE | | | OF SCOPE OF WORK. 104.6.5 ADMIN CODE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|