Plan Review Notes For Permit 02040697
Permit Number 02040697
Review Stop E
Sequence Number 1
Notes
Date Text
2002-04-29 00:00:00****************** UNSAT **************
  
 1)NOTE:PLEASE NOTE THAT ALL BRANCH
 CIRCUIT #`S ARE TO BE ON PLANS AND TO
 CORRELATE WITH A SUBMITTED PANEL
 SCHEDULE.
  
 2)NOTE: PLEASE NOTE LOAD CALCULATIONS
 NEED TO BE SUBMITTED FOR ALL NEW LOADS
 ADDED. 220 OF THE NEC. 215-5,220-3,220-
 -10,220-11,220-13. PLEASE NOTE ALL
 CONTINUOUS LOAD AT 125%. 215-2-3, 230-42
  
  
 3)NOTE: PLEASE NOTE THAT A CONTRACT
 NEEDS TO BE SUBMITTED TO VERIFY VALUE
 OF SCOPE OF WORK. 104.6.5 ADMIN CODE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372