| Plan Review Notes For Permit 02040691 |
| Permit Number |
02040691 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-05-07 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1) SHT #1 PLEASE GIVE DIMENSIONS FOR | | | EXISTING RESTROOMS. | | | 2) SHT #1 DOOR SWING SHALL NOT OPEN INTO | | | THE CLEAR FLOOR SPACE OF HDCP LAV. FBC- | | | 2001 SEC 4.17.3 | | | 3) SHT #1 SI SINK SHALL COMPLY WITH SEC | | | 11-424. GIVE DETAILS FOR ALL SUBSECTIONS | | | 4) SHTS #1 & #3 JANITOR SINK REFERED TO | | | ON SANT. RISER DIAGRAM NOT SHOWN ON DEMO | | | SHT OR FLOOR PLAN?? PLEASE SHOW JANITOR | | | SINK OF FLOOR PLAN. (TABLE 403.1 - FBC- | | | 2001 PLUMBING REQUIRES 1 SERVICE SINK). | | | 5) SHT #3 PLUMBING NOTE #7 - AIR CHAMB- | | | ERS ARE NOT APPROVED. WATER HAMMER ARRES | | | TORS ARE REQUIRED ON ALL QUICK CLOSING | | | VALVES ONLY. (WASH MACHINES, ICE MAKERS, | | | DISHWASHERS ECT.) IF USED THEY SHALL BE | | | LOCATED NEAR FIXTURE, IN AN "EFFECTIVE | | | RANGE", NOT AT TOP OF DROP. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|