| Plan Review Notes For Permit 02040690 |
| Permit Number |
02040690 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-04-24 00:00:00 | DENIED | | | REFERENCE: FBC-2001 424.2 SWIMMING POOLS | | | | | | 1) PLEASE ADJUST YOUR NOTES, DETAILS, OR | | | SUBMITTALS TO REFLECT THE FOLLOWING IN- | | | FORMATION REQUIRED FOR PLAN REVIEW. | | | A) | | | FBC-2001 SEC 424.2.6.6.2 SHOW COMPLIANCE | | | WITH ANSI/ASME A112.19.8M. PROVIDE MODEL | | | NUMBER AND MANUF INFO FOR VAC LOCK. | | | (GIVE DETAIL, ADD TO NOTES OR SUBMITTAL) | | | B) | | | FBC-2001 SEC 424.2.7.2 PUMPS AND EQUIP- | | | MENT SHALL BE MOUNTED ON A SUBSTANTIAL | | | BASE IN A MANNER THAT WILL ELIMINATE | | | STRAIN ON PIPING. SLAB SHALL BE A NOMIN- | | | AL 4" THICK. (DETAIL) | | | C) | | | FBC-2001 SEC 424.2.12.1 PRESSURE TESTS. | | | PER MANUFACTURE RECOMMENDATIONS, NO AIR | | | TEST SHALL BE APPROVED FOR PVC PIPE AND | | | FITTINGS. (ADD TO NOTES) | | | D) | | | FBC-2001 SEC 424.2.14.4 CONNECTIONS, ALL | | | WATER HEATING EQUIPMENT SHALL BE INSTAL- | | | LED WITH FLANGES OR UNION CONNECTIONS | | | ADJACENT TO THE HEATER. (ADD TO NOTES) | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|