| Notes |
| Date |
Text |
| 2002-06-10 00:00:00 | PROVISO | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE NOTE THE FOLLOWING,AND MAKE THE | | | NECESSARY CHANGES IN THE FIELD BEFORE | | | CALLING INSPECTION.ALSO CORRECT AND | | | SUBMIT "AS BUILTS" SHOWING CORRECTIONS. | | | | | | 1} BREAKERS #14 & #16 ARE SHOWN AS "GFI | | | KITCHEN RECEPT." APPLIANCE CIRCUITS ARE | | | LISTED ON THE SCHEDULE AND SHOWN ON THE | | | PLAN AS GFI,WHICH MEETS THE REQUIREMENTS | | | OF THIS REVIEW.SPACES #14 AND #16 | | | SHOULD LIST "ARC FAULT BREAKER" PER | | | 210-12. | | | | | | 2} THE #6 GROUND FROM THE METER TO THE | | | FIRST MEANS OF DISCONNECT NEEDS TO BE | | | REMOVED TO PREVENT PARALLEL PATHS TO | | | GROUND WITH THE GROUNDED CONDUCTOR. SEE | | | 250-24(A)(5). | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561/659-8096 EXT. 8392 |
|