Plan Review Notes
Plan Review Notes For Permit 02040626
Permit Number 02040626
Review Stop E
Sequence Number 2
Notes
Date Text
2002-06-10 00:00:00PROVISO
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE NOTE THE FOLLOWING,AND MAKE THE
 NECESSARY CHANGES IN THE FIELD BEFORE
 CALLING INSPECTION.ALSO CORRECT AND
 SUBMIT "AS BUILTS" SHOWING CORRECTIONS.
  
 1} BREAKERS #14 & #16 ARE SHOWN AS "GFI
 KITCHEN RECEPT." APPLIANCE CIRCUITS ARE
 LISTED ON THE SCHEDULE AND SHOWN ON THE
 PLAN AS GFI,WHICH MEETS THE REQUIREMENTS
 OF THIS REVIEW.SPACES #14 AND #16
 SHOULD LIST "ARC FAULT BREAKER" PER
 210-12.
  
 2} THE #6 GROUND FROM THE METER TO THE
 FIRST MEANS OF DISCONNECT NEEDS TO BE
 REMOVED TO PREVENT PARALLEL PATHS TO
 GROUND WITH THE GROUNDED CONDUCTOR. SEE
 250-24(A)(5).
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT. 8392