Plan Review Notes
Plan Review Notes For Permit 02040626
Permit Number 02040626
Review Stop R
Sequence Number 1
Notes
Date Text
2002-05-20 00:00:00BUILDING DENIED
  
 1)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) PROVIDE AT LEAST ONE BATHROOM WITH A
 DOOR THAT HAS A 29 INCH CLEAR OPENING,
 AS REQUIRED BY THE 2001 FLORIDA
 BUILDING CODE CHAPTER 11.
  
 3) INDICATE THE POSITIVE AND NEGATIVE
 PRESSURES FOR THE SKYLIGHT AND THE GLASS
 BLOCK OPENINGS ON THE PLANS.
  
 4) THE 8'-0" PRIVACY WALL AND THE ONE
 HOUR RATED ACCESS PANEL ARE REQUIRED TO
 REMAIN DUE TO ZERO LOT LINE WITH THE
 ADJOINING LOT. (TABLE 600)
  
 5) PLEASE REVISE DETAIL 2 ON A4 TO SHOW
 TAPERED BUCKS THAT EXTEND BEYOND THE
 FACE OF THE WINDOW FRAME AND THE FRAME
 ANCHORS THROUGH THE 1X BUCK AND INTO THE
 STRUCTURAL SUBSTRATE MATERIAL AS
 REQUIRED BY FBC SEC. 1707.4.4.2.
  
 6) THE MINIMUM BUCK SIZE DESIGN
 CLARIFICATION DETAILS FOR THE KDI
 WINDOWS DO NOT COMPLY WITH THE 2001 FBC
 SECTION 1707.4.4.2. WHEN USING 1X BUCKS
 THE ANCHORS FOR THE FRAMES ARE REQUIRED
 TO ATTACH THROUGH THE BUCKS AND INTO THE
 STRUCTURAL SUBSTRATE MATERIAL. TAPERED
 BUCKS MUST EXTEND BEYOND THE FACE OF THE
 FRAMES TO PROVIDE FULL SUPPORT OF THE
 FRAME.
  
 7) PLEASE UPDATE THE DESIGN CRITERIA ON
 SHEET S1 TO THE 2001 FBC,(ASCE 7-98, 140
 MPH. THE 2001 FBC SECTION 1606.1.7
 REQUIRES THE FOLLOWING INFORMATION TO BE
 SHOWN ON THE CONSTRUCTION DRAWINGS:
 - BASIC WIND SPEED, MPH.
 - WIND IMPORTANCE FACTOR(1) AND BUILDING
 CATEGORY.
 - WIND EXPOSURE- IF MORE THAN ONE WIND
 EXPOSURE IS USED THE WIND EXPOSURE AND
 APPLICABLE WIND DIRECTION SHALL BE
 INDICATED.
 - THE APPLICABLE INTERNAL PRESSURE
 COEFFICIENT
 - COMPONENTS AND CLADDING. THE DESIGN
 WIND PRESSURES IN TERMS OF PSF, TO BE
 USED FOR THE DESIGN OF EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE REGISTERED
 DESIGN PROFESSIONAL.
  
 8) INDICATE ON THE PLANS THAT THE WELDED
 WIRE REINFORCEMENT FABRIC WILL BE
 SUPPORTED WITH APPROVED MATERIALS OR
 SUPPORTS PER THE 2001 FBC SEC. 1909.3.
  
 9) PLEASE REVISE GENERAL NOTES (3) & (4)
 ON S4 FROM STANDARD TO FLORIDA BUILDING
 CODE.
  
 10) SBCCI EVALUATION REPORT #9733 FOR
 KDI HAS BEEN REPLACED BY # 9733A. PLEASE
 SUBMIT CURRENT REPORT.
  
 11) PRODUCT APPROVAL FOR ENTEGRA ROOF
 TILE EXPIRED ON 10-01-01. PLEASE SUBMIT
 CURRENT APPROVAL.
  
 12) THE KEY PLAN AND INSTALLATION
 SCHEDULE SUBMITTED FOR THE STORM PANELS
 IS FOR A DIFFERENT MODEL (A). PLEASE
 SUBMIT THE ONES FOR MODEL "C".
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202