| Plan Review Notes For Permit 02040626 |
| Permit Number |
02040626 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-05-07 00:00:00 | ************** UNSAT **************** | | | | | | 1 )NOTE: PLEASE LIST THE REQ`D ARC | | | FAULT PROECTED CIRCUITS ON PANEL | | | SCHEDULE. PER 210-12 | | | | | | 2)NOTE: PLEASE NOTE GARAGE OUTLET TO BE | | | SHOWN AS GFI/GFI PROTECTED. PER 210-8 | | | | | | 3)NOTE: PLEASE NOTE THAT PLANS ARE SHOW- | | | ING A MAIN DISCONNECT NEXT TO METERCAN | | | AND NEXT TO PANEL INSIDE GARAGE?? | | | PLEASE CLARIFY WHICH ONE? IF ANY? PLEASE | | | NOTE THAT RISER DIAGRAM SHOWS MAIN DISC | | | OUTSIDE. | | | | | | 4)NOTE: PLEASE NOTE THAT MIN SIZING OF | | | OCP AND WIRE FOR A 10KW AHU. PER 424-3B | | | | | | 5)NOTE: PLEASE NOTE THAT AN OVEN AND | | | COOKTOP IS SHOWN ON PANEL SCHEDULE AND | | | ONLY THE COOKTOP IS ON LOAD CALCULATIONS | | | PLEASE ADD TO LOAD CALCS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE NAY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|