Plan Review Notes
Plan Review Notes For Permit 02040623
Permit Number 02040623
Review Stop R
Sequence Number 1
Notes
Date Text
2002-05-17 00:00:00BUILDING DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) INDICATE THE POSTITIVE AND NEGATIVE
 PRESSURES FOR THE SKYLIGHT ON THE PLANS.
  
 3)PLEASE REVIEW THE POSTIVE AND NEGATIVE
 PRESSURES THAT ARE GIVEN FOR THE DOORS
 AND WINDOWS THE APPEAR TO BE INCORRECT.
 (TOO HIGH)
  
 4) PLEASE REVIEW THE M.O. LISTED FOR THE
 1/2 33SH WINDOW, IT IS TOO LARGE.
  
 5) INDICATE ON THE PLANS THAT THE WELDED
 WIRE REINFORCEMENT FABRIC WILL BE
 SUPPORTED WITH APPROVED MATERIALS OR
 SUPPORTS PER 2001 FBC SEC. 1909.3.
  
 6) REVISE ITEM #2 ON A1 TO REFERENCE THE
 FLORIDA BUILDING CODE.
  
 7) THE CALCULATIONS FOR THE OPENINGS
 ALLOWED BY TABLE 600 CONTAINS SEVERAL
 ERRORS. THE AREA ALLOWED AS OPENINGS IS
 52.3 SQFT. AND OPENINGS TOTAL 54.4 SQFT.
 PLEASE CORRECT.
  
 8) PLEASE REVISE DETAIL 2 ON A4 TO SHOW
 TAPERED BUCKS EXTENDING BEYOND THE FACE
 OF WINDOW AND DOOR FRAMES TO PROVIDE
 FULL SUPPORT OF THE FRAME AND ANCHORS
 FOR WINDOW/DOOR FRAMES THROUGH THE 1X
 BUCKS AND INTO THE STRUCTURAL SUBSTRATE
 MATERIAL AS REQUIRED BY THE FBC SECTION
 1707.4.4.2.
  
 9) THE 2001 FBC SECTION 1606.1.7
 REQUIRES THE FOLLOWING INFORMATION TO BE
 SHOWN ON THE CONSTRUCTION DRAWINGS:
 - BASIC WIND SPEED, MPH.
 - WIND IMPORTANCE FACTOR(1) AND BUILDING
 CATEGORY.
 - WIND EXPOSURE- IF MORE THAN ONE WIND
 EXPOSURE IS USED THE WIND EXPOSURE AND
 APPLICABLE WIND DIRECTION SHALL BE
 INDICATED.
 - THE APPLICABLE INTERNAL PRESSURE
 COEFFICIENT
 - COMPONENTS AND CLADDING. THE DESIGN
 WIND PRESSURES IN TERMS OF PSF, TO BE
 USED FOR THE DESIGN OF EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE REGISTERED
 DESIGN PROFESSIONAL.
 PLEASE UPDATE THE STRUCTURAL DESIGN
 INFORMATION ON S1.
  
 10) THE PARTY WALL DETAILS 6 & 8 ON S3
 SHOULD INDICATE THAT THE FIRE RETARDANT
 PLYWOOD IS REQUIRED TO EXTEND 4 FEET ON
 EACH SIDE THE WALLS PER 704.4(2) FBC.
  
 11) PLEASE UPDATE THE NOTES ON S4 TO
 REFERENCE THE 2001 FLORIDA BUILDING CODE
 THEY HAVE BEEN MARKED ON PLANS.
  
 12) THE SBCCI EVALUATION REPORT (PRODUCT
 APPROVAL) FOR KDI DOORS AND WINDOWS HAS
 BEEN UPDATED BY REPORT #9733A. PLEASE
 SUBMIT CURRENT REPORT.
  
 13) THE BUCK ATTACHMENT DETAILS DO NOT
 COMPLY WITH 1707.4.4.2 OF THE 2001 FBC.
 PLEASE SUBMIT REVISED DRAWINGS.
  
 14) PROVIDE ORIGINAL DATED, SIGNED AND
 SEALED COPY OF THE SINGLE HUNG WINDOW
 ANALYSIS CHART AND ENGINEER'S
 CALCULATIONS FOR KDI WINDOWS.
  
 15) THE PRODUCT APPROVAL FOR THE ENTEGRA
 ROOF TILE EXPIRED ON 10-01-01. SUBMIT
 CURRENT PRODUCT APPROVAL.
  
 16) PLEASE REVIEW THE OPENING SIZES ON
 THE STORM PANEL INSTALLATION SCHEDULE
 AND REVISE TO MATCH WINDOW OPENINGS AS
 NECESSARY.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202
  
 TRUSSES UNSAT
  
 1) PLEASE REVIEW THE CONNECTOR FOR JOINT
 2 ON TRUSS TG1. THE TRUSS DRAWING LISTS
 AN UPLIFT OF 4381# AND THE PLANS SHOW A
 TA5 RATED FOR 2490#.
  
 2) THE STANDARD GABLE END DETAIL HAS THE
 INNCORRECT DESIGN CRITERIA. PLEASE
 UPDATE TO 2001 FLORIDA BUILDING CODE AND
 ASCE 7-98.