| Date |
Text |
| 2002-05-17 00:00:00 | BUILDING DENIED |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) INDICATE THE POSTITIVE AND NEGATIVE |
| | PRESSURES FOR THE SKYLIGHT ON THE PLANS. |
| | |
| | 3)PLEASE REVIEW THE POSTIVE AND NEGATIVE |
| | PRESSURES THAT ARE GIVEN FOR THE DOORS |
| | AND WINDOWS THE APPEAR TO BE INCORRECT. |
| | (TOO HIGH) |
| | |
| | 4) PLEASE REVIEW THE M.O. LISTED FOR THE |
| | 1/2 33SH WINDOW, IT IS TOO LARGE. |
| | |
| | 5) INDICATE ON THE PLANS THAT THE WELDED |
| | WIRE REINFORCEMENT FABRIC WILL BE |
| | SUPPORTED WITH APPROVED MATERIALS OR |
| | SUPPORTS PER 2001 FBC SEC. 1909.3. |
| | |
| | 6) REVISE ITEM #2 ON A1 TO REFERENCE THE |
| | FLORIDA BUILDING CODE. |
| | |
| | 7) THE CALCULATIONS FOR THE OPENINGS |
| | ALLOWED BY TABLE 600 CONTAINS SEVERAL |
| | ERRORS. THE AREA ALLOWED AS OPENINGS IS |
| | 52.3 SQFT. AND OPENINGS TOTAL 54.4 SQFT. |
| | PLEASE CORRECT. |
| | |
| | 8) PLEASE REVISE DETAIL 2 ON A4 TO SHOW |
| | TAPERED BUCKS EXTENDING BEYOND THE FACE |
| | OF WINDOW AND DOOR FRAMES TO PROVIDE |
| | FULL SUPPORT OF THE FRAME AND ANCHORS |
| | FOR WINDOW/DOOR FRAMES THROUGH THE 1X |
| | BUCKS AND INTO THE STRUCTURAL SUBSTRATE |
| | MATERIAL AS REQUIRED BY THE FBC SECTION |
| | 1707.4.4.2. |
| | |
| | 9) THE 2001 FBC SECTION 1606.1.7 |
| | REQUIRES THE FOLLOWING INFORMATION TO BE |
| | SHOWN ON THE CONSTRUCTION DRAWINGS: |
| | - BASIC WIND SPEED, MPH. |
| | - WIND IMPORTANCE FACTOR(1) AND BUILDING |
| | CATEGORY. |
| | - WIND EXPOSURE- IF MORE THAN ONE WIND |
| | EXPOSURE IS USED THE WIND EXPOSURE AND |
| | APPLICABLE WIND DIRECTION SHALL BE |
| | INDICATED. |
| | - THE APPLICABLE INTERNAL PRESSURE |
| | COEFFICIENT |
| | - COMPONENTS AND CLADDING. THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF, TO BE |
| | USED FOR THE DESIGN OF EXTERIOR |
| | COMPONENT AND CLADDING MATERIALS NOT |
| | SPECIFICALLY DESIGNED BY THE REGISTERED |
| | DESIGN PROFESSIONAL. |
| | PLEASE UPDATE THE STRUCTURAL DESIGN |
| | INFORMATION ON S1. |
| | |
| | 10) THE PARTY WALL DETAILS 6 & 8 ON S3 |
| | SHOULD INDICATE THAT THE FIRE RETARDANT |
| | PLYWOOD IS REQUIRED TO EXTEND 4 FEET ON |
| | EACH SIDE THE WALLS PER 704.4(2) FBC. |
| | |
| | 11) PLEASE UPDATE THE NOTES ON S4 TO |
| | REFERENCE THE 2001 FLORIDA BUILDING CODE |
| | THEY HAVE BEEN MARKED ON PLANS. |
| | |
| | 12) THE SBCCI EVALUATION REPORT (PRODUCT |
| | APPROVAL) FOR KDI DOORS AND WINDOWS HAS |
| | BEEN UPDATED BY REPORT #9733A. PLEASE |
| | SUBMIT CURRENT REPORT. |
| | |
| | 13) THE BUCK ATTACHMENT DETAILS DO NOT |
| | COMPLY WITH 1707.4.4.2 OF THE 2001 FBC. |
| | PLEASE SUBMIT REVISED DRAWINGS. |
| | |
| | 14) PROVIDE ORIGINAL DATED, SIGNED AND |
| | SEALED COPY OF THE SINGLE HUNG WINDOW |
| | ANALYSIS CHART AND ENGINEER'S |
| | CALCULATIONS FOR KDI WINDOWS. |
| | |
| | 15) THE PRODUCT APPROVAL FOR THE ENTEGRA |
| | ROOF TILE EXPIRED ON 10-01-01. SUBMIT |
| | CURRENT PRODUCT APPROVAL. |
| | |
| | 16) PLEASE REVIEW THE OPENING SIZES ON |
| | THE STORM PANEL INSTALLATION SCHEDULE |
| | AND REVISE TO MATCH WINDOW OPENINGS AS |
| | NECESSARY. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |
| | |
| | TRUSSES UNSAT |
| | |
| | 1) PLEASE REVIEW THE CONNECTOR FOR JOINT |
| | 2 ON TRUSS TG1. THE TRUSS DRAWING LISTS |
| | AN UPLIFT OF 4381# AND THE PLANS SHOW A |
| | TA5 RATED FOR 2490#. |
| | |
| | 2) THE STANDARD GABLE END DETAIL HAS THE |
| | INNCORRECT DESIGN CRITERIA. PLEASE |
| | UPDATE TO 2001 FLORIDA BUILDING CODE AND |
| | ASCE 7-98. |