| Plan Review Notes For Permit 02040623 |
| Permit Number |
02040623 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-05-07 00:00:00 | ***************** UNSAT *************** | | | | | | 1 )NOTE: PLEASE LIST THE REQ`D ARC | | | FAULT PROECTED CIRCUITS ON PANEL | | | SCHEDULE. PER 210-12 | | | | | | 2)NOTE: PLEASE CLARIFY, PLANS SHOW A | | | MAIN DISCONNECT INSIDE WITH PANEL AND | | | OUTSIDE WITH METER? WHICH ONE? PLEASE | | | NOTE RISER DIAGRAM SHOWS MAIN OUTSIDE. | | | | | | 3)NOTE: PLEASE NOTE THAT PANEL SCHEDULE | | | SHOWS AN OVEN AND YET LOAD CALCULATIONS | | | DO NOT INCLUDE OVEN. PLEASE INCLUDE. | | | | | | 4)NOTE: PLEASENOTE OCP AND WIRE FOR | | | AHU NEEDS TO BE SIZED FOR 10KW PER | | | 424-3B MIN125%. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-80096 EXT 8372 |
|