| Plan Review Notes For Permit 02040598 |
| Permit Number |
02040598 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-06-10 00:00:00 | ******************DENIED**************** | | | | | | COMMENTS FROM PREVIOUS REVIEW NOT | | | ADDRESSED. | | | | | | NO MECHANICAL PLANS SUBMITTED FOR | | | REVIEW.INDICATE EQUIPMENT (NEW OR | | | EXISTING), DUCTWORK & GRILLES (NEW, | | | EXISTING, RELOCATED), CFM DISTRIBUTION. | | | PROVIDE OUTSIDE AIR CALCULATIONS AS | | | PER 62-89.SHOW CCOMPLIANCE FOR AIR | | | BALANCE AS PER 2001 FBC(M) 601.4. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|