Plan Review Notes
Plan Review Notes For Permit 02040598
Permit Number 02040598
Review Stop P
Sequence Number 1
Notes
Date Text
2002-05-04 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING & CHAPT. 11
  
 1) ALL PLANS DESIGNED BY AN ARCHITECT
 SHALL BE SEALED, SIGNED, & DATED - FS/
 FAC 481.221 - FS 61G1-16.003 IF USED FOR
 PUBLIC RECORD.
 2) PLEASE SUPPLY ALL MEASUREMENTS FOR
 TOILET ROOMS.
 3) PLEASE SHOW CLEAR FLOOR SPACE FOR ALL
 HDCP FIXTURES.
 4) HDCP WATER CLOSETS SHALL BE 1'6" OFF
 WALL, HDCP LAVS SHALL BE 1'3" OFF WALL.
 HDCP W/C'S SHALL BE 17" TO 19" TO SEAT,
 LAVS SHALL BE 2'10" TO FLOOD RIM LEVEL
 ALL PIPING UNDER LAV TO BE INSULATED.
 5) WATER RISER DIAGRAM REQUIRED.
 6) PER MINIMUM FACILITIES TABLE 403.1
 A SERVICE SINK IS REQUIRED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377