| Plan Review Notes For Permit 02040598 |
| Permit Number |
02040598 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-04-11 00:00:00 | **************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE CLARIFY SERVICE LOCATION? | | | PLEASE NOTE GROUPING OF MAINS AND/OR | | | FIRE SEPARATION BETWEEN UNITS A,B,C | | | AT 2HRS. | | | | | | 2)NOTE: PLEASE NOTE THAT PLANS ARE NOT | | | SEALED BY THE ARCH OF RECORD. FS/FAC | | | 481.221. | | | | | | 3)NOTE: PLEASE NOTE THAT AIC RATINGS | | | WERE SUBMITTED FOR PANELS, BUT NOT FOR | | | MAIN DISC`S. PLEASE SUBMIT. | | | | | | 4)NOTE: PLEASE PROVIDE ROOM IDENTIFICAT- | | | ION FOR FLOOR LAYOUT. | | | | | | 5)NOTE: PLEASE NOTE THAT ALL CONTINUOUS | | | LOADS NEED TO BE SHOWN AT 125%. | | | 215-2/3, 230-42 ETC. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|