| 2002-04-23 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT # 02040593 |
| | 632 HIBISCUS STREET |
| | |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | 1)- FLBLD CODE 1606.1.7 INFORMATION |
| | ON DRAWINGS, MINIMUM INFO REQUIRED FOR |
| | WIND. |
| | |
| | 2)- SHEET A-1.02 INDICATES NEW DOOR |
| | OPENINGS ON THE BACK EXTERIOR OF THE |
| | BUILDING. (COMPONENTS & CLADDING) |
| | FL BLD CODE 1707.4 EXTERIOR WINDOW & |
| | DOOR ASSEMBLIES, PROVIDE PRODUCT APPROV- |
| | ALS FOR NEW DOOR OPENINGS, SBCCI OR DADE |
| | COUNTY PRODUCT TESTING REPORT.2 COPIES. |
| | |
| | 3)- FL BLD CODE 1707.4.4 ANCHORAGE |
| | METHOD, THIS APPLIES TO WINDOWS & DOOR |
| | ASSEMBLIES THAT FASTEN TO THE MAIN FORCE |
| | RESISTING SYSTEM. MISSING FASTENER AND |
| | FREQUENCY? |
| | |
| | 4)- FL BLD CODE 104.2.1.2 ADDITIONAL |
| | DATA REQUIRED, IS THE STOREFRONT |
| | SYSTEM AN EXISTING SYSTEM? OR IS THIS |
| | NEW WORK? IF NEW WORK THE SAME PRODUCT |
| | TESTING REPORT SHALL BE REQUIRED. |
| | IF NEW WORK, LARGE MISSLE IMPACT TESTING |
| | SHALL APPLY, IMPACT GLAZING OR SHUTTERS |
| | |
| | 5)- PROVIDE THE POSITVIE & NEGATIVE |
| | PRESSURS THAT APPLY TO THESE OPENINGS |
| | BEING AFFECTED. |
| | |
| | 6)- SHEET A-1.01 DETAILS 1,2 & 4 PLEASE |
| | PROVIDE THE UL RATING FOR THE ASSEMBLIES |
| | WHERE A 1 HR RATING IS ACHIEVED WITH |
| | DRYWALL ON 1 SIDE, WHEN NEXT TO STRUCTUR |
| | AL COLUMN W/ FOAM SPRAY APPLIED. |
| | |
| | 7)- FL BLD CODE 1909.3 CONCRETE SLABS |
| | ON GRADE, (2) CONCRETE SLABS ON GRADE |
| | CONTAINING 6X6 W1.4XW1.4 WELDED WIRE REI |
| | NFORCEMENT FABRIC LOCATED IN THE MIDDLE |
| | TO UPPER 1/3RD OF THE SLAB SHALL HAVE |
| | APPROVED MATERIALS OR SUPPORTS AT SPAC- |
| | ING NOT TO EXCEED 3 FT OR IN ACCORDANCE |
| | WITH THE MANUFACTURERS SPEC. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | (561)659-8096X8412 |
| | |
| | THIS IS FOR THE SLAB, STEEL FRAMING, |
| | DEMISING |