Plan Review Notes
Plan Review Notes For Permit 02040521
Permit Number 02040521
Review Stop R
Sequence Number 2
Notes
Date Text
2002-06-26 00:00:00BUILDING DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE STRUCTURE IS LOCATED IN AN 'A8'
 FLOOD ZONE. AN ELEVATION CERTIFICATE
 WILL BE REQUIRED.
  
 3) PROVIDE SOIL BEARING TEST REPORT PER
 CITY OF WPB AMENDMENTS TO 2001 FBC SEC.
 1804.2.2.
  
 4) PROVIDE ADDITIONAL COPIES OF PRODUCT
 APPROVALS FOR THE FRONT DOOR AND GLASS
 BLOCK. TWO COPIES ARE REQUIRED.
  
 5) PROVIDE TESTING INFORMATION WHICH
 INDICATES THAT THE GLASS BLOCK TO BE
 INSTALLED ON THE ZERO LOT LINE HAS A ONE
 HOUR FIRE RATING.
  
 6) PROVIDE (2) COPIES OF INSTALLATION
 SCHEDULE FOR STORM PANELS. THESE ITEMS
 ARE REQUIRED AT TIME OF PERMIT OR YOU
 WILL BE REQUIRED TO PULL A SEPARATE
 PERMIT AND PAY ADDITIONAL FEES.
  
 7) PLEASE CHANGE THE CALL SIZE OF THE
 EGRESS WINDOW (I) IN THE WINDOW SCHEDULE
 TO 24-5 SH WHICH CORRESPONDS TO THE
 REVISED DIMENSIONS GIVEN.
  
 8) PLEASE CHANGE NOTE #6 UNDER GENERAL
 NOTES ON A2 TO REFERENCE THE 2001
 FLORIDA PLUMBING CODE.
  
 9) PROVIDE A DETAIL INDICATING ONE HOUR
 FIRE RATING BASED ON BOTH INTERIOR AND
 EXTERIOR FIRE EXPOSURE FOR THE GABLE END
 ON THE ZERO LOT LINE.
  
 10) PLEASE INSERT REVISED PAGES INTO THE
 PLANS AND REMOVE OLD SHEETS. SUBMIT THE
 OLD SHEETS WITH THE NEW PLANS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202