| 2002-06-26 00:00:00 | BUILDING DENIED |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) THE STRUCTURE IS LOCATED IN AN 'A8' |
| | FLOOD ZONE. AN ELEVATION CERTIFICATE |
| | WILL BE REQUIRED. |
| | |
| | 3) PROVIDE SOIL BEARING TEST REPORT PER |
| | CITY OF WPB AMENDMENTS TO 2001 FBC SEC. |
| | 1804.2.2. |
| | |
| | 4) PROVIDE ADDITIONAL COPIES OF PRODUCT |
| | APPROVALS FOR THE FRONT DOOR AND GLASS |
| | BLOCK. TWO COPIES ARE REQUIRED. |
| | |
| | 5) PROVIDE TESTING INFORMATION WHICH |
| | INDICATES THAT THE GLASS BLOCK TO BE |
| | INSTALLED ON THE ZERO LOT LINE HAS A ONE |
| | HOUR FIRE RATING. |
| | |
| | 6) PROVIDE (2) COPIES OF INSTALLATION |
| | SCHEDULE FOR STORM PANELS. THESE ITEMS |
| | ARE REQUIRED AT TIME OF PERMIT OR YOU |
| | WILL BE REQUIRED TO PULL A SEPARATE |
| | PERMIT AND PAY ADDITIONAL FEES. |
| | |
| | 7) PLEASE CHANGE THE CALL SIZE OF THE |
| | EGRESS WINDOW (I) IN THE WINDOW SCHEDULE |
| | TO 24-5 SH WHICH CORRESPONDS TO THE |
| | REVISED DIMENSIONS GIVEN. |
| | |
| | 8) PLEASE CHANGE NOTE #6 UNDER GENERAL |
| | NOTES ON A2 TO REFERENCE THE 2001 |
| | FLORIDA PLUMBING CODE. |
| | |
| | 9) PROVIDE A DETAIL INDICATING ONE HOUR |
| | FIRE RATING BASED ON BOTH INTERIOR AND |
| | EXTERIOR FIRE EXPOSURE FOR THE GABLE END |
| | ON THE ZERO LOT LINE. |
| | |
| | 10) PLEASE INSERT REVISED PAGES INTO THE |
| | PLANS AND REMOVE OLD SHEETS. SUBMIT THE |
| | OLD SHEETS WITH THE NEW PLANS. |
| | |