Plan Review Notes
Plan Review Notes For Permit 02040521
Permit Number 02040521
Review Stop R
Sequence Number 1
Notes
Date Text
2002-05-29 00:00:00BUILDING DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) INDICATE THE APPLICABLE INTERNAL
 PRESSURE COEFFICIENT ON THE PLANS AS
 REQUIRED BY 2001 FBC SEC. 1606.1.7.
  
 3) THE STRUCTURE IS LOCATED IN AN "A8"
 FLOOD ZONE. AN ELEVATION CERTIFICATE
 WILL BE REQUIRED.
  
 4) THE ENERGY CALCULATIONS ARE REQUIRED
 TO BE SIGNED BY THE OWNER/AGENT.
  
 5) PROVIDE SOIL BEARING TEST REPORT PER
 CITY OF WPB AMENDMENTS TO 2001 FBC SEC.
 1804.2.2.
  
 6)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - FRONT DOOR (THE ONE SUBMITTED IS
 LIMITED TO DOORS WITH SIDELITES)
 - STRUCTURAL WINDOW MULLIONS
 - GLASS BLOCK ( NEED SBCCI OR METRO-DADE
 APPROVALS OR SITE SPECIFIC ENGINEERING )
  
 7) THE GLASS BLOCK LOCATED IN THE WALL
 ON THE ZERO LOT LINE IS REQUIRED TO HAVE
 A ONE HOUR FIRE RATING.
  
 8)PROVIDE A KEY PLAN AND AN INSTALLATION
 SCHEDULE FOR THE STORM PANELS. INDICATE
 THE TYPE OF FASTENERS THAT WILL BE USED.
  
 9) SHEET A2 MAKES REFERENCES TO SEVERAL
 CODES THAT WERE REPLACED BY THE FLORIDA
 BUILDING CODE 2001 EDITION. PLEASE
 UPDATE THESE REFERENCES.
  
 10) THE SH24 WINDOW IN THE SECOND FLOOR
 MASTER SUITE WILL NOT PROVIDE THE 24"
 NET CLEAR OPENING HEIGHT REQUIRED FOR
 EGRESS BY 1005.4.4 OF THE FBC.
  
 11) THE ONE HOUR FIRE RATING OF THE
 EXTERIOR WALL ON THE ZERO LOT LINE MUST
 BE MAINTAINED WHERE THE FLOOR GIRDER
 TRUSS ENTERS THE WALL AS INDICATED ON
 SHEET S1. IF THIS TRUSS DOES NOT
 PENETRATE THE WALL, INDICATE AN
 APPROPRIATE HANGER.
  
 12)THE FOUNDATION PLAN ON S1 INCORRECTLY
 STATES THAT TERMITE TREATMENT IS PER 97
 SBC. PLEASE CORRECT TO 2001 FBC SEC.1816
  
 13) NOTE # 14 ON A5 INDICATES 3"X 24"
 ATTIC VENTS AND THE CALCULATIONS USE
 6"X 24" ATTIC VENTS. PLEASE CORRECT.
  
 14) PLEASE INDICATE THE CONNECTORS THAT
 WILL BE USED TO ANCHOR THE KING HIP
 TRUSSES AT THE BUILDING CORNERS ON SHEET
 S1.
  
 15) PLEASE CLARIFY IF THE COMMON TRUSSES
 ON S1 WILL BE ANCHORED AT EACH END WITH
 TC-5 CONNECTORS.
  
 16) ON SHEET S2 ITEM #3 UNDER "CODE"
 STATES THAT UPLIFT IS DESIGNED IN
 ACCORDANCE WITH SBC CODE 1997 ED. THE
 2001 FBC REQUIRES DESIGN BASED ON
 ASCE 7-98 OR SECTION 1606.2 OF THE 2001
 FBC. PLEASE REVISE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202