Plan Review Notes
Plan Review Notes For Permit 02040521
Permit Number 02040521
Review Stop E
Sequence Number 1
Notes
Date Text
2002-04-26 00:00:00**************** UNSAT **************
  
 1)NOTE: PLEASE NOTE PLANS STILL SHOWING
 96 NEC CODE ARTS. PLEASE CORRELATE
 W/ 99 NEC.
  
 2)NOTE: PLEASE NOTE MISPRINT FOR AIC
 RATING, SHOWN AS 22.00, INSTEAD OF
 22,000.
  
 3 )NOTE: PLEASE CLARIFY EQUIPMENT
 GROUNDING METHOD BETWEEN FIRST MEANS
 OF DISCONNECT AND PANELS. PLEASE SIZE
 CONDUCTORS PER 250-122.
  
 4))NOTE: PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE/NOTES. PER 210-12
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372