| Plan Review Notes For Permit 02040521 |
| Permit Number |
02040521 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-04-26 00:00:00 | **************** UNSAT ************** | | | | | | 1)NOTE: PLEASE NOTE PLANS STILL SHOWING | | | 96 NEC CODE ARTS. PLEASE CORRELATE | | | W/ 99 NEC. | | | | | | 2)NOTE: PLEASE NOTE MISPRINT FOR AIC | | | RATING, SHOWN AS 22.00, INSTEAD OF | | | 22,000. | | | | | | 3 )NOTE: PLEASE CLARIFY EQUIPMENT | | | GROUNDING METHOD BETWEEN FIRST MEANS | | | OF DISCONNECT AND PANELS. PLEASE SIZE | | | CONDUCTORS PER 250-122. | | | | | | 4))NOTE: PLEASE LIST THE REQ`D ARC | | | FAULT PROTECTED CIRCUITS ON PANEL | | | SCHEDULE/NOTES. PER 210-12 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|