| 2002-06-27 00:00:00 | BUILDING DENIED |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) THE STRUCTURE IS LOCATED IN AN "A8" |
| | FLOOD ZONE. AN ELEVATION CERTIFICATE |
| | WILL BE REQUIRED. |
| | |
| | 3) PROVIDE A SOIL BEARING TEST REPORT |
| | PER CITY OF WPB AMENDMENTS TO THE 2001 |
| | FBC SEC. 1804.2.2. |
| | |
| | 4) PROVIDE (2) COPIES OF INSTALLATION |
| | SCHEDULE FOR STORM PANELS. THESE ARE |
| | REQUIRED AT TIME OF PERMIT OR A SEPARATE |
| | PERMIT (WITH ADDITIONAL FEES) WILL HAVE |
| | TO BE PULLED FOR THE STORM PANELS. |
| | |
| | 5) PROVIDE ADDITIONAL COPIES OF PRODUCT |
| | APPROVALS FOR THE FRONT DOOR AND GLASS |
| | BLOCK. TWO COPIES ARE REQUIRED. |
| | |
| | 6) PROVIDE TESTING INFORMATION FOR GLASS |
| | BLOCK WHICH INDICATES BLOCK HAS A ONE |
| | HOUR FIRE RATING. |
| | |
| | 7) PLEASE CHANGE THE CALL SIZE OF THE |
| | EGRESS WINDOW (I) IN THE WINDOW SCHEDULE |
| | TO 24-5 SH WHICH CORRESPONDS TO THE |
| | REVISED DIMENSIONS GIVEN. |
| | |
| | 8) PLEASE CHANGE NOTE #6 UNDER GENERAL |
| | NOTES ON A2 TO REFERENCE THE 2001 |
| | FLORIDA PLUMBING CODE. |
| | |
| | 9) PROVIDE A DETAIL OF THE GABLE END ON |
| | THE ZERO LOT LINE. IT IS REQUIRED TO BE |
| | A ONE HOUR FIRE RATED ASSEMBLY BASED ON |
| | BOTH INTERIOR AND EXTERIOR EXPOSURE TO |
| | FIRE. |
| | |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |