Plan Review Notes
Plan Review Notes For Permit 02040516
Permit Number 02040516
Review Stop R
Sequence Number 2
Notes
Date Text
2002-06-24 00:00:00BUILDING DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE STRUCTURE IS LOCATED IN AN "A8"
 FLOOD ZONE AN ELEVATION CERTIFICATE
 WILL BE REQUIRED.
  
 3) PROVIDE SOIL BEARING TEST REPORT PER
 FBC SEC. 1804.2.2.
  
 4) PROVIDE MANUFACTURER'S SPECIFICATIONS
 AND TESTING INFORMATION FOR ONE HOUR
 FIRE RATED GLASS BLOCK.
  
 5) PROVIDE AN INSTALLATION SCHEDULE FOR
 STORM PANELS OR APPLY UNDER A SEPARATE
 PERMIT AND PAY ADDITIONAL PERMIT FEES.
  
 6) PROVIDE ADDITIONAL COPIES OF PRODUCT
 APPROVALS FOR THE FRONT DOOR AND GLASS
 BLOCK. TWO COPIES OF EACH ARE REQUIRED.
  
 7) PROVIDE A DETAIL OF THE GABLE END ON
 THE ZERO LOT LINE. IT IS REQUIRED TO
 HAVE A ONE HOUR FIRE RATING BASED ON
 BOTH INTERIOR AND EXTERIOR EXPOSURE TO
 FIRE. SEE 2001 FBC TABLE 600 AND NOTE I.
  
 8) PLEASE CHANGE THE CALL SIZE OF THE
 EGRESS WINDOW (I) IN THE WINDOW SCHEDULE
 TO 24-5 SH WHICH CORRESPONDS WITH THE
 REVISED DIMENSION THAT IS GIVEN.
  
 9) PLEASE CHANGE NOTE #6 UNDER GENERAL
 NOTES ON A2 TO REFERENCE THE 2001
 FLORIDA PLUMBING CODE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202