| Date |
Text |
| 2002-05-16 00:00:00 | BUILDING DENIED |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) INDICATE THE APPLICABLE INTERNAL |
| | PRESSURE COEFFICIENT ON THE PLANS AS |
| | REQUIRED BY 2001 FBC 1606.1.7. |
| | |
| | 3) THE STRUCTURE IS LOCATED IN AN "A8" |
| | FLOOD ZONE AN ELEVATION CERTIFICATE WILL |
| | BE REQUIRED. |
| | |
| | 4) THE ENERGY CALCULATIONS ARE REQUIRED |
| | TO BE SIGNED BY THE OWNER/AGENT. |
| | |
| | 5) FL BLD CODE 1804.2.2 QUESTIONABLE |
| | SOILS, WHERE THE BEARING CAPACITY IS |
| | NOT DEFINETLY KNOWN OR IS IN QUESTION. |
| | PROVIDE SOIL BEARING TEST REPORT. |
| | |
| | 6)PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - FRONT DOOR (THE ONE SUBMITTED IS FOR A |
| | DOOR WITH SIDELITES ONLY AS STATED IN |
| | THE LIMITATIONS) |
| | - GLASS BLOCK (INFO SUBMITTED IS NOT |
| | ACCEPTABLE) |
| | |
| | 7) THE GLASS BLOCK LOCATED IN THE WALL |
| | ON THE ZERO LOT LINE IS REQUIRED TO |
| | HAVE A ONE HOUR FIRE RATING. |
| | |
| | 8)PROVIDE A KEY PLAN AND AN INSTALLATION |
| | SCHEDULE FOR STORM PANELS. INDICATE THE |
| | TYPE OF FASTENERS THAT WILL BE USED. |
| | |
| | 9) ON SHEET A2 SEVERAL REFERENCES ARE |
| | MADE TO CODES WHICH HAVE BEEN REPLACED |
| | BY THE 2001 FLORIDA BUILDING CODE. |
| | PLEASE CORRECT. |
| | |
| | 10) THE SH24 WINDOW IN THE SECOND FLOOR |
| | MASTER SUITE WILL NOT PROVIDE A 24" NET |
| | CLEAR OPENING HEIGHT REQUIRED FOR EGRESS |
| | PER 1005.4.4. THE SH34 WINDOWS USED FOR |
| | EGRESS MUST BE SIZED AS INDICATED IN THE |
| | WINDOW SCHEDULE IN ORDER TO COMPLY. |
| | |
| | 11) PLEASE INDICATE THAT THE ANCHORS FOR |
| | THE WINDOWS AND SLIDING GLASS DOORS ARE |
| | REQUIRED TO FASTEN THROUGH THE 1X BUCKS |
| | INTO THE STRUCTURAL SUBSTRATE MATERIAL. |
| | SEE BUCK DETAILS ON A5. |
| | |
| | 12) THE ONE HOUR FIRE RATING OF THE |
| | EXTERIOR WALL ON THE ZERO LOT LINE MUST |
| | BE MAINTAINED WHERE THE FLOOR GIRDER |
| | TRUSS ENTERS THE WALL AS INDICATED ON |
| | SHEET S1. IF THIS TRUSS DOES NOT |
| | PENETRATE INTO THE WALL, INDICATE AN |
| | APPROPRIATE HANGER. |
| | |
| | 13)THE FOUNDATION PLAN ON S1 INCORRECTLY |
| | STATES THAT TERMITE TREATMENT IS PER |
| | 97SBC. PLEASE CORRECT. SEE 2001FBC 1816. |
| | |
| | 14) PLEASE INDICATE THE CONNECTORS THAT |
| | WILL BE USED TO ANCHOR THE KING HIP |
| | TRUSSES AT THE BUILDING CORNERS ON S1. |
| | |
| | 15) PLEASE CLARIFY IF THE COMMON TRUSSES |
| | ON S1 WILL BE ANCHORED AT EACH END WITH |
| | TC-5 CONNECTORS. |
| | |
| | 16) ON SHEET S2 ITEM #3 UNDER "CODE" |
| | STATES THAT UPLIFT IS DESIGNED IN |
| | ACCORDANCE WITH SBC CODE 1997 ED. THE |
| | 2001 FBC REQUIRES DESIGN BASED ON |
| | ASCE 7-98 OR SECTION 1606.2 OF THE 2001 |
| | FBC. PLEASE REVISE. |
| | |
| | PLEASE MAKE CORRECTIONS TO UPDATE THE |
| | MASTER CAD DRAWING SO THAT FUTURE PLANS |
| | SUBMITTED FOR PERMIT WILL BE CORRECT. |
| | |
| | IF YOU HAVE ANY QUESTIONS PLEASE CALL: |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |