Plan Review Notes
Plan Review Notes For Permit 02040516
Permit Number 02040516
Review Stop R
Sequence Number 1
Notes
Date Text
2002-05-16 00:00:00BUILDING DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) INDICATE THE APPLICABLE INTERNAL
 PRESSURE COEFFICIENT ON THE PLANS AS
 REQUIRED BY 2001 FBC 1606.1.7.
  
 3) THE STRUCTURE IS LOCATED IN AN "A8"
 FLOOD ZONE AN ELEVATION CERTIFICATE WILL
 BE REQUIRED.
  
 4) THE ENERGY CALCULATIONS ARE REQUIRED
 TO BE SIGNED BY THE OWNER/AGENT.
  
 5) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 PROVIDE SOIL BEARING TEST REPORT.
  
 6)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - FRONT DOOR (THE ONE SUBMITTED IS FOR A
 DOOR WITH SIDELITES ONLY AS STATED IN
 THE LIMITATIONS)
 - GLASS BLOCK (INFO SUBMITTED IS NOT
 ACCEPTABLE)
  
 7) THE GLASS BLOCK LOCATED IN THE WALL
 ON THE ZERO LOT LINE IS REQUIRED TO
 HAVE A ONE HOUR FIRE RATING.
  
 8)PROVIDE A KEY PLAN AND AN INSTALLATION
 SCHEDULE FOR STORM PANELS. INDICATE THE
 TYPE OF FASTENERS THAT WILL BE USED.
  
 9) ON SHEET A2 SEVERAL REFERENCES ARE
 MADE TO CODES WHICH HAVE BEEN REPLACED
 BY THE 2001 FLORIDA BUILDING CODE.
 PLEASE CORRECT.
  
 10) THE SH24 WINDOW IN THE SECOND FLOOR
 MASTER SUITE WILL NOT PROVIDE A 24" NET
 CLEAR OPENING HEIGHT REQUIRED FOR EGRESS
 PER 1005.4.4. THE SH34 WINDOWS USED FOR
 EGRESS MUST BE SIZED AS INDICATED IN THE
 WINDOW SCHEDULE IN ORDER TO COMPLY.
  
 11) PLEASE INDICATE THAT THE ANCHORS FOR
 THE WINDOWS AND SLIDING GLASS DOORS ARE
 REQUIRED TO FASTEN THROUGH THE 1X BUCKS
 INTO THE STRUCTURAL SUBSTRATE MATERIAL.
 SEE BUCK DETAILS ON A5.
  
 12) THE ONE HOUR FIRE RATING OF THE
 EXTERIOR WALL ON THE ZERO LOT LINE MUST
 BE MAINTAINED WHERE THE FLOOR GIRDER
 TRUSS ENTERS THE WALL AS INDICATED ON
 SHEET S1. IF THIS TRUSS DOES NOT
 PENETRATE INTO THE WALL, INDICATE AN
 APPROPRIATE HANGER.
  
 13)THE FOUNDATION PLAN ON S1 INCORRECTLY
 STATES THAT TERMITE TREATMENT IS PER
 97SBC. PLEASE CORRECT. SEE 2001FBC 1816.
  
 14) PLEASE INDICATE THE CONNECTORS THAT
 WILL BE USED TO ANCHOR THE KING HIP
 TRUSSES AT THE BUILDING CORNERS ON S1.
  
 15) PLEASE CLARIFY IF THE COMMON TRUSSES
 ON S1 WILL BE ANCHORED AT EACH END WITH
 TC-5 CONNECTORS.
  
 16) ON SHEET S2 ITEM #3 UNDER "CODE"
 STATES THAT UPLIFT IS DESIGNED IN
 ACCORDANCE WITH SBC CODE 1997 ED. THE
 2001 FBC REQUIRES DESIGN BASED ON
 ASCE 7-98 OR SECTION 1606.2 OF THE 2001
 FBC. PLEASE REVISE.
  
 PLEASE MAKE CORRECTIONS TO UPDATE THE
 MASTER CAD DRAWING SO THAT FUTURE PLANS
 SUBMITTED FOR PERMIT WILL BE CORRECT.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved