| Plan Review Notes For Permit 02040516 |
| Permit Number |
02040516 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-04-26 00:00:00 | ****************** UNSAT ************* | | | | | | 1)NOTE: PLEASE NOTE THAT CODE ARTS ARE | | | FROM 96 NEC, PLEASE CORRELATE TO THE | | | 99 NEC. | | | | | | 2)NOTE: PLEASE NOTE MIS PRINT FOR AIC | | | RATING. SHOWN AS 22.00? SHOULD SHOW | | | 22,000. | | | | | | 3 )NOTE: PLEASE CLARIFY EQUIPMENT | | | GROUNDING METHOD BETWEEN FIRST MEANS | | | OF DISCONNECT AND PANELS. PLEASE SIZE | | | CONDUCTORS PER 250-122. | | | | | | 4 )NOTE: PLEASE LIST THE REQ`D ARC | | | FAULT PROTECTED CIRCUITS IN NOTES OR | | | ON PANEL SCHEDULE. PER 210-12 | | | | | | PLEASE SUBMIT TTHE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|