Plan Review Notes
Plan Review Notes For Permit 02040516
Permit Number 02040516
Review Stop E
Sequence Number 1
Notes
Date Text
2002-04-26 00:00:00****************** UNSAT *************
  
 1)NOTE: PLEASE NOTE THAT CODE ARTS ARE
 FROM 96 NEC, PLEASE CORRELATE TO THE
 99 NEC.
  
 2)NOTE: PLEASE NOTE MIS PRINT FOR AIC
 RATING. SHOWN AS 22.00? SHOULD SHOW
 22,000.
  
 3 )NOTE: PLEASE CLARIFY EQUIPMENT
 GROUNDING METHOD BETWEEN FIRST MEANS
 OF DISCONNECT AND PANELS. PLEASE SIZE
 CONDUCTORS PER 250-122.
  
 4 )NOTE: PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS IN NOTES OR
 ON PANEL SCHEDULE. PER 210-12
  
 PLEASE SUBMIT TTHE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372