Plan Review Notes For Permit 02040506
Permit Number 02040506
Review Stop E
Sequence Number 2
Notes
Date Text
2002-06-28 00:00:00 
 UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE NECESSARY CHANGES TO
 PLANS,AND RESUBMIT FOR REVIEW.
  
 1} PROVIDE LOAD CALCULATIONS FOR ALL
 ADDITIONAL LOADS PER 220-3(C) NEC.
  
 2} NOTE:BATH,WET BAR,AND OUSIDE
 RECEPTACLES TO BE GFI PER
 210-8(A)(1),(3),&(7).PLEASE INDICATE
 SAME ON PLANS.
  
 3} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PLAN PER
 210-12
  
 4} CLOSET IN THE MASTER BEDROOM SHOWS AN
 A/C UNIT,THE DISCONNECT MUST COMPLY
 WITH 110-26,PLEASE SHOW LOCATION ON
 PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL;
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT. 8392