| Plan Review Notes For Permit 02040494 |
| Permit Number |
02040494 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-07-12 00:00:00 | | | | NOT APPROVED | | | | | | 1] | | | THE WRONG BUILDING CODE IS NOTED UNDER | | | THE WIND CRITERIA. | | | | | | 2] | | | PLEASE SPECIFY WHICH ROOF COVER WILL BE | | | USED, PLAN CALLS FOR TWO DIFFERENT | | | KINDS. | | | | | | 3] | | | ROOF FRAMING, 2X4 RAFTERS MAXIMUM SPAN | | | IS 7'5", PLAN NOT IN COMPLIANCE. | | | | | | 4] | | | CLARIFY RIDGE BEAM, 2X6 OR 2X8. | | | | | | 5] | | | DESIGNER SHALL NOTE ON PLAN THAT THE | | | COVERED TERRACE WILL NOT BE ATTACHED TO | | | EXISTING STRUCURES. | | | | | | | | | LUIS MARTINEZ | | | 659-8096 | | | #8456 |
|