| 2005-03-11 00:00:00 | ****CORRECTIONS**** |
| | REVISIONS 46, 50, 58 |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | THE REVISIONS 46 THROUGH 59 SUBMITTED |
| | WERE NOT CLOUDED WITH THE EXCEPTION OF |
| | THE MOST CURRENT REVISION. I WAS UNABLE |
| | TO LOCATE SOME OF THE CHANGES ON THE |
| | PLAN, NOTED BELOW. |
| | |
| | 1.)SHEET A8.06, 22.2, IDENTIFY AND |
| | CLARIFY 4X4 1 HR ACCESS PANEL. |
| | |
| | 2.)SHEET A8.06, 22.3, CMU WALL |
| | RELOCATED, IDENTIFY. |
| | |
| | 3.)SHEET A8.31, 43.3 AND 43.6, UNCLEAR |
| | FROM TRANSMITTAL AS TO WHAT CHANGED. |
| | |
| | 4.)SHEET A11.03, IS THIS DETAIL 13? |
| | SPECIFY FIRE RATING REQUIREMENT AND SHOW |
| | COMPLIANCE. |
| | |
| | 5.)DRAWING A8.23, 35.2.IT IS UNCLEAR |
| | WHY THE 1 HR WALL WAS ADDED AS IT IS NOT |
| | CONTINUOUS AROUND THE ENTIRE STORAGE |
| | ROOM AREA.ALSO THE SEPARATION |
| | REQUIREMENT FOR STORAGE LOW HAZARD IS 2 |
| | HR FBC704.1 IF IT IS REQUIRED.SEE |
| | FBC704.1.2.2(4). |
| | |
| | REVISION #50 DATED 7/21/2004 |
| | |
| | 6.)A3.10, THE RAILING DETAIL SHOWS A 2 |
| | 1/2" DISTANCE BETWEEN THE BOTTOM RAIL |
| | AND THE SLAB.THE GUARDRAIL IS TO |
| | COMPLY WITH FBC1015.3, TO REJECT A 2" |
| | OBJECT (7-A3.10 SHOWS 2 1/2"), AND IT IS |
| | NOT CLEAR IF THE 6 1/2" DISTANCE FROM |
| | BOTTOM OF BOTTOM RAIL TO TOP OF NEXT |
| | RAIL IS COMPLIANT WITH THE REQUIREMENT |
| | TO REJECT A 4" OBJECT. |
| | |
| | 7.)A A11.12, DETAILS 6 AND 7, PROVIDE |
| | DESIGN CRITERIA.THE DESIGN FOR THE |
| | HANDRAIL IS TO COMPLY WITH FBC1608.2.1, |
| | THE GUARDRAIL IS TO COMPLY WITH |
| | FBC1608.2.2. |
| | |
| | 8.)IT IS NOT CLEAR HOW THE NEW DETAILS |
| | TIE INTO THE OLD DETAIL (8), OR WHERE |
| | THEY ARE TO BE INSTALLED. THE GUARDRAIL |
| | SHOWS A HANDRAIL.IF THIS IS NOT A |
| | GUARDRAIL WHICH IS ALSO A STAIR RAIL, IS |
| | THE HANDRAIL REQUIRED?THE DISTANCE |
| | BETWEEN THE HANDRAIL (AT 2'10") AND THE |
| | SUPPORTS FOR THE TOP RAIL APPEARS TOO |
| | NARROW (REQUIREMENT BETWEEN A HANDRAIL |
| | AND WALL IS 1 1/2").IT IS DIFFICULT TO |
| | DETERMINE CODE COMPLIANCE AS I AM UNSURE |
| | AS TO THE APPLICATION OF THE DETAILS. |