| Plan Review Notes For Permit 02040459 |
| Permit Number |
02040459 |
|
| Review Stop |
M |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2004-08-20 00:00:00 | DENIED: | | | 1.PLAN SHEET M2.02 INDICATES REV #3 ON | | | THE PLAN BUT DOES NOT INDICATE THE DATE | | | OF THE REVISION ON THE REVISION SCHEDULE | | | OR THE DRAWING NARRATIVE. | | | | | | 2.PLAN SHEET M2.04 UNIT 11L DOES NOT | | | INDICATE RETURN AIR FROM BEDROOM #2. | | | | | | 3.PLAN SHEET 2.35 & M5.05, PLANS | | | INDICATE 2 COOLING TOWERS DELETED & | | | MANUFACTURER CHANGED.PROVIDE SUBMITTAL | | | FOR REVISED COOLING TOWER. | | | | | | 4.PLEASE NOTE THIS CHANGE ALSO AFFECTS | | | THE ENERGY CALCULATIONS PLEASE REVISE | | | ENERGY CALCS. | | | | | | 5.TONNAGE & GPM CHANGED ON THE COOLING | | | TOWER, PLEASE PROVIDE CALCULATIONS | | | DEMONSTRATING THAT THEY WILL MEET THE | | | DEMAND. | | | | | | 5.PLEASE NOTE MECHANICAL JOINTS | | | (VICTALIC FITTINGS, COUPLINGS, ETC) ARE | | | TO BE READYLY ACCESSIBLE. 2001 FBC(M) | | | 1209.3. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|