| Plan Review Notes For Permit 02040459 |
| Permit Number |
02040459 |
|
| Review Stop |
P |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2003-08-11 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | FHA-98 DESIGN MANUAL | | | | | | 1) RISERS 43/55/44/12 6TH THROUGH 10TH | | | FLOOR. WHEN A HORIZONTAL STACK OFFSET IS | | | LOCATED MORE THAN FOUR BRANCH INTERVALS | | | BELOW THE TOP OF THE STACK, A HORIZONTAL | | | BRANCH SHALL NOT CONNECT WITHIN THE | | | HORIZONTAL STACK OFFSET OR WITHIN 2 FEET | | | ABOVE OR BELOW SUCH OFFSET. SEC 711.2 | | | SHT P3.16 (WASH MACHINE) | | | 2) RISER #1 SEE COMMENT #1 (BATHROOM AND | | | SINK) SHT P3.14 | | | 3) RISER #2 6TH FLOOR W/M DRAINS THROUGH | | | BATHROOM GROUP. SEC 909.1 SHTP3.14 ALSO | | | RISERS 53/50/51 | | | 4) RISERS 34/58/25 KITCHEN SINK CONNECT- | | | ED IN HORIZONTAL OFFSET. (SEE COMMENT # | | | 1) | | | 5) RISER #13 SHT P3.16 KITCHEN SINK | | | CONNECTED IN OFFSET. (SEE COMMENT #1) | | | 6) RISER #52 SAME AS RISER #1. | | | 7) SECTION 917.3.2 RELIEF VENT REQUIRED | | | TO AIR ADMITTANCE VALVES. ALL 8 A.A.V'S | | | WILL WILL REQUIRE A RELIEF VENT. | | | 8) PLANS SHALL BE PICKED UP AND RESUB- | | | MITTED. PER CITY CODE A 10% RESUB FEE | | | WILL BE REQUIRED. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|