| Date |
Text |
| 2003-08-15 00:00:00 | 1) ON SHEET E2.01 NEAR STAIR # 1 EXIT |
| | SIGNS APPEAR TO OPPOSE ONE ANOTHER. |
| | SHEET E2.02 APPEARS TO HAVE THE |
| | SAME PROBLEM. |
| | |
| | 2) THE LIFE SAFETY SYSTEM NOTES ON |
| | PAGE E2.03 INDICATES EQUIPMENT THAT |
| | WILL BE CONTAINED IN THE FIRE |
| | COMMAND CENTER AND AT THE CONCEIRGE |
| | DESK. PLEASE REVIEW FIRE COMMAND |
| | STATION REQUIREMENTS IN THE FLORIDA |
| | BUILDING CODE AND INCLUDE ALL |
| | REQUIRED DEVICES IN THIS ROOM. THE |
| | CONCEIRGE DESK IS NOT MENTIONED IN |
| | THIS CODE SECTION AND THEREFORE NOT |
| | ACCEPTABLE. |
| | |
| | 3) A SPEAKER STROBE IS NOT DESIRED IN |
| | THE FIRE COMMAND CENTER. |
| | |
| | 4) ARE ANY EMERGENCY LIGHTS PRESENT |
| | IN THE MEZZANINE LEVEL AREA 1, TENANT |
| | STORAGE BINS SEEN ON PAGE E2.06. |
| | |
| | 5) NO SMOKE DETECTORS SHOWN IN UNIT |
| | 18L AND 19L. |
| | |
| | 6) TENANT STORAGE BINS LOCATED ON |
| | MEZZANINE LEVEL AREA II DOES NOT |
| | ALLOW FOR THE REQUIRED 44" HALLWAY |
| | CLEARANCE. PLEASE EXPLAIN, PAGE E2.07. |
| | |
| | 7) SMOKE DETECTOR MISSING FROM |
| | ELECTRICAL ROOM MEZZANINE LEVEL AREA |
| | II, PAGE E2.07. |
| | |
| | 8) UNIT 36 DOES NOT DISPLAY A SMOKE |
| | DETECTOR ON PAGE E2.15. |
| | |
| | 9) ANY EMERGENCY LIGHTS OR EXIT SIGNS |
| | PRESENT IN TENANT STORAGE TOWER LEVEL |
| | 6, PAGE E.2.21. |
| | |
| | 10) SMOKE DETECTOR(S) APPEAR TO BE |
| | MISSING IN BEDROOM # 2 IN UNIT B7. |
| | |
| | 11) EXIT SIGN ON PAGE E2.42 IS LEADING |
| | PERSONS THRU A SOLID WALL. |
| | |
| | 12) IT APPEARS ON PAGE E2.42 THAT ONLY |
| | ONE DOOR IS IDENTIFIED BY AN EXIT SIGN. |
| | |
| | 13) FIRE SPRINKLER HEADS ARE REQUIRED |
| | AT THE TOP OF ALL SHAFTS. PLEASE SEE |
| | REVISION # 10 ON PAGE LS 100 WHICH |
| | IS INCORRECT. |
| | |
| | 14) PLANS STILL DISPLAY A 1000 GPM FIRE |
| | PUMP. A 1250 GPM FIRE PUMP IS THE |
| | MINIMUM SIZE THAT WILL BE ACCEPTED. |
| | |
| | 15) ALL SHAFTWAYS LARGE ENOUGH FOR |
| | PERSONS TO FALL INTO MUST BE MARKED |
| | SHAFTWAY IN 6" HIGH LETTERS. |
| | |
| | 16) ARCHITECTURAL TRIM ON OUTSIDE OF |
| | BUILDING SHALL BE NON-COMBUSTIBLE. |
| | |
| | APPROVED PROVISO. NEW SHEETS WITH |
| | SIGNED AND SEALED LETTERS ARE TO BE |
| | SUBMITTED WITH CORRECTIONS. |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| | 835-2910 |
| | 805-6722 |