| 2004-06-01 00:00:00 | ****CORRECTIONS**** |
| | ARCHITECTURAL REVISION, VARIOUS |
| | SHEETS, DATED 4/12/04 |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | 1.)SHEET A1.04 SHOWS TWO SLOPES |
| | GREATER THAN 1:50, NOT COMPLIANT WITH |
| | FBC11-4.6.3. (SEE REVIEW SET) |
| | |
| | 2.)SHEET A2.02 IS NOT SIGNED AND |
| | SEALED ON REVIEW SET. |
| | |
| | 3.)SHEET A1.06, AT 17'5" ELEVATION, |
| | STAIR 3, WHAT IS THE PURPOSE OF THE |
| | DOOR IN THE MIDDLE OF THE STAIR LANDING? |
| | |
| | 4.)THE REVISIONS AFFECT MEPS.SUBMIT |
| | THE REVISIONS AS NECESSARY. |
| | |
| | 5.)SHEETS 5.08 AND 5.09, WHERE IS |
| | THE DETAIL FOR THE METAL STUD WALLS? |
| | THE RECENT STRUCTURAL REVISION |
| | SUBMITTED SHOWS THESE WALLS AS A TYPE |
| | W3, CONCRETE WALL.TRANSMITTAL LETTER |
| | INDICATES THE WALLS AS "SHOWN WITHOUT |
| | CONCRETE - TO BE METAL STUD |
| | CONSTRUCTION."PLEASE CLARIFY. |
| | |
| | 6.) A3.09 REFERS TO FOAM COLUMN AND |
| | PANEL.ARCHITECTURAL TRIM ON BUILDINGS |
| | LOCATED IN THE FIRE DISTRICT SHALL BE |
| | CONSTRUCTED OF APPROVED NONCOMBUSTIBLE |
| | MATERIALS OR FIRE RETARDANT TREATED |
| | WOOD, F102.2.7 CITY OF WEST PALM BEACH |
| | AMENDMENTS TO THE FBC, FBC1404. |
| | |
| | 7.)PROVIDE CALCULATIONS FOR STAIR |
| | #5, THE NEW EGRESS STAIR, TO SHOW |
| | COMPLIANCE WITH FBC412.11(5). |
| | |
| | 8.)DOORS IN THE STAIRWAY ENCLOSURES |
| | ARE TO COMPLY WITH FBC705.1.3.4. |
| | |
| | 9.)PROVIDE A DETAIL FOR TYPE I |
| | REFERRED TO ON SHEET 5.12 (2 HR SHAFT). |
| | |
| | 10.) SHEET 6.04, PROVIDE A CONSTRUCTION |
| | DETAIL, INCLUDING METHOD OF ATTACHMENT |
| | TO THE BUILDING, FASTENING CONNECTION |
| | DETAILS. |
| | |
| | 11.) TRASH CHUTES SHALL COMPLY WITH |
| | NFPA82 3-2.4.3.1, THE SIZE OF THE |
| | SERVICE OPENING ROOM OR COMPARTMENT |
| | SHALL NOT BE LESS THAN THAT REQUIRED TO |
| | MAINTAIN A MINIMUM OF 6" CLEARANCE |
| | BETWEEN THE OPEN LOADING DOOR AND THE |
| | CLOSED SERVICE OPENING ROOM DOOR. |