| Date |
Text |
| 2003-06-02 00:00:00 | 1) PLEASE PROVIDE MORE INFORMATION WITH |
| | REGARDS TO GLASS IN LOBBY DOORS THAT ARE |
| | PROTECTED WITH A SPRINKLER HEAD ON EACH |
| | SIDE OF GLASS. WATER CURTAINS ARE NOT |
| | DESIGNED TO PROTECT DOORS. PLEASE |
| | PROVIDE RECOGNIZED TEST DATA. |
| | |
| | 2) ALL EXIT STAIRS THAT TERMINATE INTO |
| | EXIT PASSAGEWAYS SHALL HAVE THE SAME |
| | FIRE PROTECTION RATING AS THE STAIRS. |
| | |
| | 3) THE PLAN PROPOSED A 1000 GPM FIRE |
| | PUMP. AGAIN THIS INFORMATION DOES NOT |
| | APPEARS TO BE CORRECT. ALL REQUIRED |
| | STAIRS FOR THE BUILDING SHALL HAVE |
| | STANDPIPE CONNECTIONS. IF EIGHT STAIRS |
| | ARE REQUIRED, THEN IN REALITY A 1000 GPM |
| | FIRE PUMP IS NOT LARGE ENOUGH. PLEASE |
| | ADVISE. |
| | |
| | 4) PLEASE EXPLAIN GATES AND CARD READERS |
| | AND HOW DO THEY AFFECT EXITING. |
| | |
| | 5) PLEASE EXPLAIN OPEN UNPROTECTED |
| | STAIRS. |
| | |
| | 6) PLEASE PROVIDE FIRE RATING FOR STAIR |
| | # 10. |
| | |
| | 7) STAIR # 5 APPEARS TO BE OPEN PLEASE |
| | EXPLAIN RATIONALE. |
| | |
| | 8) HOW DO YOU DIRECT PEOPLE VIA STAIRS |
| | ACROSS AREAS OF PARKING TO REACH |
| | ENCLOSED EXIT STAIRS. |
| | |
| | 9) MORE DETAILS NEEDED ON ROUND FORM |
| | COLUMNS SHOWN ON A3.01. |
| | |
| | 10) KNOX-BOXES ARE TO BE INSTALLED ON |
| | THE EXTERIOR OF THE BUILDING. |
| | |
| | 11) EXIT ACCESS ON MAIN ROOF LEVEL PLAN |
| | NOTED THRU DEDICATED AREA FOR LEASABLE |
| | SPACE. |
| | |
| | 12) EXPANDED POLYSTYRENE NOTED IN |
| | BUILDING SECTIONS 3 & 3A. |
| | |
| | 13) PLEASE PROVIDE INFO ON 1" INSULATION |
| | AROUND TRASH CHUTE. |
| | |
| | 14) PLEASE EXPLAIN WHY EXITING ON LS 102 |
| | GOES THRU BICYCLE STORAGE AND WHAT CODE |
| | REFERENCE ALLOWS THIS. |
| | |
| | 15) SMOKE DETECTORS ARE REQUIRED IN ALL |
| | MECHANICAL, ELECTRICAL, TRANSFORMER AND |
| | TELEPHONE EQUIPMENT ROOMS PER 412.2 . |
| | |
| | NATE MCCRAY, CAPTAIN |
| | 659-8096, EXT 8497 |
| | 805-6722 OR 835-2910 |