| Plan Review Notes For Permit 02040459 |
| Permit Number |
02040459 |
|
| Review Stop |
E |
| Sequence Number |
23 |
|
| Notes |
| Date |
Text |
| 2005-09-19 00:00:00 | REVISION 66 | | | | | | PAGE 2.02SUBMIT DETAIL ON LOW VOLTAGE | | | TRANSFORMER FOR LOW VOLTAGE | | | ROPE LIGHTINGSIZE OF TRANS | | | OVERCURRENT PROTECTION. | | | SHOW LOCATION OF TRANS, DISC. | | | | | | PAGE 3.026TH FLOOR ELECTRICAL ROOM | | | SHOWS NEW TRANSFORMER WHAT | | | DOES IT FEED? | | | IF THE CHANGE IS ONLY ONE | | | TRANSFORMER PLEASE DON'T | | | CLOUD WHOLE ROOM TAKES A LONG | | | TIME TO FIGURE OUT WHAT THE | | | CHANGE IS!!!!!!!!!! | | | | | | PAGE 4.016TH FLR CHANGE NOT SHOWN ON | | | RISER. | | | | | | NOTE K-8 ??? WHAT SIZE CKT. | | | BREAKER IS A 150 HP ??????? | | | |
|