| 2003-03-18 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 11 |
| | FHA-98 DESIGN MANUAL |
| | |
| | 1) SHT P2.01 VENT REQUIRED FOR FLOOR |
| | DRAIN IN TRASH ROOM. |
| | 2) ALL UNITS - WET VENTS IN BATHROOMS, |
| | ONLY THE FIXTURES WITHIN THE BATHROOM |
| | GROUPS SHALL CONNECT TO THE WET-VENTED |
| | HORIZONTAL BRANCH DRAIN. ANY ADDIDIONAL |
| | FIXTURES SHALL DISCHARGE DOWNSTREAM OF |
| | THE WET VENT. (KITCHEN SINKS AND WASH- |
| | MACHINES SHALL NOT DRAIN THROUGH BATH- |
| | ROOMS) SECTION 909.1 - THESE CONDITIONS |
| | SHALL BE CORRECTED ON THE SANITARY RISER |
| | DIAGRAMS AND ALL FLAT LAYOUTS. |
| | 3) SHT P2.01 RAIN WATER LEADER IS NOT |
| | SIZED PROPERLY. UNIT 27L |
| | 4) SHT P2.01 PROVIDE AREA BEING DRAINED |
| | AT TRENCH DRAINS. |
| | 5) SHT P2.01 SECTION 504.7.1 THE DIS- |
| | CHARGE PIPE SHALL NOT HAVE ANY TRAPPED |
| | SECTIONS AND SHALL HAVE A VISIBLE AIR |
| | GAP. (RELIEF VALVE FOR HEATER) |
| | 6) SHT P2.01 PROVIDE CALCULATIONS FOR |
| | CONDENSATE FROM UNITS TO DETERMINE PIPE |
| | SIZE. |
| | 7) P2.04 4" SANT. AT RISERS 37, 22, 57, |
| | & 38 SHOWS 4" @ 420 F.U. (MAX 180 F.U.) |
| | 8) SHT P2.04 UNISEX TOILET - NO SANT. TO |
| | W/C AND LAV. |
| | 9) SHT P2.05 SHOW PIPE SIZE FOR RWL PAST |
| | TRASH ROOM. |
| | 10) SHT P2.05 SHOW PIPE SIZE FOR COND. |
| | TO TRASH ROOM. |
| | 11) SHT P2.11 MAX DISTANCE FOR W/C IS 10 |
| | FEET. TABLE 906.1 |
| | 12) SHT P2.18 UNIT #3, SHOW PIPE SIZE |
| | FOR HORIZONTAL RWL. (1900 SQ FT) |
| | 13) SHT P2.19 UNIT B3 SHOW PIPE SIZE FOR |
| | HORIZONTAL RWL. (2900 SQ FT) |
| | 14) SHT P2.22 UNIT B6, SHOW PIPE SIZE |
| | FOR HORIZONTAL RWL. (2000 SQ FT) |
| | 15) NEAR UNIT B7, RWL NOT SIZED PROPERLY |
| | SHOULD BE 890 SQ FT FOR BOTH SIDES. 1980 |
| | SQ FT TOTAL. |
| | 16) SHT P2.31 HORIZONTAL RWL NOT SIZED |
| | PROPERLY. SHOWS 4" @ 2900 & 2800 SQ FT. |
| | 17) SHT P2.33 UNIT M, 3 DD @ 600 SQ FT |
| | EACH = 1800 SQ FT. 1500 SQ FT SHOWN. |
| | PIPE SIZED WRONG. |
| | 18) SHT P2.34 UNIT O, 6" RWL DOWN SHOWS |
| | 600 SQ FT. ADDS UP TO 2900 SQ FT. PLEASE |
| | ADJUST PLANS. |
| | 19) SHT P2.39 PLEASE SUBMIT CALCULATIONS |
| | FOR PRIMARY AND SECONDARY ROOF DRAINS. |
| | SHOW ALL AREAS OF ROOFS THAT DRAIN TO |
| | ROOF FROM ABOVE.SHOW 1/2 AREA OF ALL |
| | VERTICAL WALLS, INCLUDING PARAPET WALLS. |
| | INDICATE TOTAL AREA OF MAIN ROOF. SHOW |
| | LOCATION OF ALL SECONDARY ROOF DRAINS & |
| | INDICATE AREA BEING DRAINED BY EACH. |
| | PROVIDE A DETAIL FOR SCUPPERS SHOWING |
| | LENGTH - WIDTH - HEIGHT - SEE SECTIONS |
| | 1106, 1106.4, 1106.5, 1107, 1107.1, |
| | 1107,2 & 1107.3 |
| | 20) SHT P2.44 POOL DECK WATER RISERS, |
| | AIR CHAMBERS ARE NOT APPROVED. PLEASE |
| | DELETE FROM RISERS. |
| | 21) SHTS P2.40 & P2.41, SHOW TOTAL F.U. |
| | FOR COMBINED SANITARY RISERS THAT VENT |
| | THRU ROOF TOGETHER. |
| | 22) SHT P2.44 SHOW PIPE SIZE FOR RWL. |
| | SHOWS 6" @ 4000 SQ FT. WHEN ADDED IT |
| | COMES TO 5000 SQ FT AND 6" IS NOT SUFFI- |
| | CIENT. |
| | 23) SHT P2.45 GARAGE EXHAUST CHASE, WHAT |
| | WILL BE DRAINING INTO THE FLOOR DRAIN IN |
| | THE BOTTOM? |
| | 24) SHT P2.45 VENT REQUIRED FOR FLOOR |
| | DRAIN IN BREEZEWAY DRIVE. |
| | 25) SHT P2.45 VENTS REQUIRED FOR FLOOR |
| | DRAINS IN TRASH ROOM AND TRASH TERMINA- |
| | TION ROOM. |
| | 26) SHT P2.49 SQ FOOTAGE NOT CALCULATED |
| | PROPERLY FOR RWL BY PARKING SPACE 495. |
| | 450 + 220 + 220 = 440 SQ FT ??? |
| | 890 + 890 = 1780 SQ FT NOT 1330. 5" PIPE |
| | IS REQUIRED. |
| | 27) SHT P2.49 MORE INFORMATION REQUIRED |
| | FOR WATER WALL. |
| | 28) SHTS P3.02, P3.03, P3.04, P3.05, |
| | P3.06, P3.07 & P3.08 AIR CHAMBERS ARE |
| | NOT APPROVED. PLEASE DELETE FROM RISERS. |
| | WATER HAMMER ARRESTORS REQUIRED BY SEC. |
| | 406.9 SHALL BE LOCATED NEAR THE FIXTURE, |
| | NOT IN CEILING PER PDI-WH 201 AND MANUF. |
| | INSTALLATION INSTRUCTIONS. (WASH MACHINE |
| | ICE MAKER, & DISHWASHER). |
| | 29) SHT P3.09 RWL RISER SHOWS 4" @ 1500 |
| | SQ FT & 4" @ 2900 SQ FT ON SAME RISER. |
| | PLEASE CLAIRFY. |
| | 30) SHT P3.09 RWL RISER SHOWS 4" @ 1900 |
| | SQ FT ON VERTICAL. BUT RISER ALSO RUNS |
| | HORIZONTAL, (OFFSET). 5" RISER REQUIRED. |
| | 31) SHT P3.10 RWL BY DECK, NO PIPE SIZE |
| | SHOWN. |
| | 32) SHT P3.10 RWL RISER SHOWS 5" @ 5100 |
| | SQ FT, BUT RISER ALSO RUNS HORIZONTAL. |
| | 8" RISER REQUIRED. |
| | 33) SHT P3.10 RWL RISER SHOWS 5" @ 3000 |
| | SQ FT PICKING UP 2 ROOF DRAINS. RUNS |
| | HORIZONTAL, 6" REQUIRED. |
| | 34) SHT P3.10 PIPE SIZE NOT SHOWN FOR |
| | RWL PIPE IN SOME AREAS. |
| | 35) SHT P3.10 PROVIDE AREA BEING DRAINED |
| | BY TRENCH DRAINS. |
| | 36) SHT P3.10 RWL RISER SHOWS 6" @ 6900 |
| | SQ FT. RUNS HORIZONTAL, 8" RISER REQD. |
| | 37) SHT P3.10 RWL RISER SHOWS 5" @ 5700 |
| | SQ FT. RUNS HORIZONTAL, 8" RISER REQD. |
| | 38) SHTS P3.11 & P3.12 RELIEF VENTS RE- |
| | QUIRED AS CONDENSATE EXITS BLDG. |
| | 39) SHT P3.13 FLOOR DRAINS NOT VENTED. |
| | 40) SHTS P3.14 & P3.15 SOIL AND WASTE |
| | STACKS IN BUILDINGS HAVING MORE THAN 10 |
| | BRANCH INTERVALS SHALL BE PROVIDED WITH |
| | A RELIEF VENT AT EACH TENTH INTERVAL IN- |
| | STALLED, BEGINNING WITH THE TOP FLOOR. |
| | SECTION 914.1 |
| | 41) SHTS P3.14/P3.15 HORIZONTAL OFFSETS |
| | OF DRAINAGE STACKS SHALL BE VENTED WHERE |
| | FIVE OR MORE BRANCH INTERVALS ARE LOCAT- |
| | ED ABOVE THE OFFSET. THE OFFSET SHALL BE |
| | VENTED BY VENTING THE UPPER SECTION OF |
| | THE DRAINAGE AND THE LOWER SECTION OF |
| | THE DRAINAGE STACK. SECTION 915.1 |
| | UPPER SECTION SECTION 915.2 LOWER 915.3 |
| | ALSO SEE SECTION 903.4 |
| | 42) SHTS P3.14/P3.15 IF A HORIZONTAL |
| | BRANCH CONNECTS TO THE STACK WITHIN 2 FT |
| | ABOVE OR BELOW A VERTICAL AND THE OFFSET |
| | IS LOCATED MORE THAN FOUR BRANCH INTER-V |
| | ALS BELOW THE TOP OF THE STACK, THE OFF- |
| | SET SHALL BE VENTED IN ACCORDANCE WITH |
| | SECTION 915. SECTION 711.1 |
| | 43) SHTS P3.14/P3.15 WHEN A HORIZONTAL |
| | STACK OFFSET IS LOCATED MORE THAN FOUR |
| | BRANCH INTERVALS BELOW THE TOP OF THE |
| | STACK, A HORIZONTAL BRANCH SHALL NOT |
| | CONNECT WITHIN THE HORIZONTAL STACK OFF- |
| | SET OR WITHIN 2 FEET ABOVE OR BELOW SUCH |
| | OFFSET. SECTION 711.2 - SEE SECTIONS |
| | 711.3, SECTION 914, 710.1.1, TABLE |
| | 710.1(2) COL 4, SECTION 711.3.1 & SECT- |
| | ION 711.4. |
| | 44) SHT A5.11 FOUNTAIN EQUIPMENT AREA |
| | NOT SHOWN ON PLUMBING. MORE INFORMATION |
| | AND DETAILS REQUIRED. |
| | 45) SHT A5.11A SHOWS POOL EQUIPMENT AREA |
| | IN THE SAME AREA AS THE FOUNTAIN EQUIP. |
| | AREA SHT A5.11. PLEASE CLAIRFY. |
| | 46) SHTS A8.01 THRU A8.05 DOOR SHALL NOT |
| | OPEN INTO THE CLEAR FLOOR SPACE OF ANY |
| | FIXTURE OR THE 5' TURNING CIRCLE. PLEASE |
| | CHANGE AS REQUIRED. |
| | 47) SHTS A8.01 THRU A8.05 ALL LIVE/WORK |
| | LOFTS SHALL HAVE A DRINKING FOUNTAIN PER |
| | TABLE 403.1. (ALSO SEE 410.1) |
| | 48) SHTS A8.01 THRU A8.14 SHOW CLEAR |
| | FLOOR SPACE FOR ALL FIXTURES PER FHA |
| | DESIGN MANUAL PAGE 7.43 & CHAPTER 11 FBC |
| | 49) SHTS A8.12/A8.13 TERRACE DRAINS NOT |
| | SHOWN ON PLUMBING PLANS. SCUPPER DETAILS |
| | NOT SHOWN. PLEASE SUBMIT DETAILS AND |
| | CALL OUT DRAINS ON PLUMBING PLANS. |
| | 50) SHTS A8.13, A8.14, A8.19 THRU A8.39 |
| | PER FHA DESIGN MANUAL, INDICATE SPECI- |
| | FICATION "A" OR "B" PER REQUIREMENT #7 |
| | FOR ALL UNITS. |
| | 51) SHT A8.26 MENS RESTROOM L106, SHOW |
| | CLEAR FLOOR SPACE FOR URNAL. |
| | 52) PLEASE SUBMIT ALL SANITARY RISER |
| | DIAGRAMS. 37 RISERS ARE NOT SHOWN. |
| | MISSING ARE #'S 8 THRU 10, 12 THRU 15, |
| | 17 THRU 20, 22 THRU 29, 31, 32, 34 THRU |
| | 44, & 55 THRU 59. |
| | 53) PLEASE CONTACT RODNEY COMPO, ENVIRO- |
| | NMENTAL COMPLIANCE TO SEE IF AN OIL |
| | SEPARATOR IS REQUIRED FOR TRENCH DRAINS. |
| | 54) SHT A5.16 PLEASE SUBMIT DETAILS FOR |
| | STEAM ROOM L117. |
| | 55) PLEASE SUBMIT RISERS FOR RELIEF |
| | VALVE DISCHARGE,(T/P), AND EMERGENCY PAN |
| | DRAIN LINES FOR WATER HEATERS. INDICATE |
| | TYPE OF MATERIAL USED AND ALL PIPE SIZE- |
| | ING. - SHOW THERMAL EXPANSION CONTROL ON |
| | WATER HEATER DETAIL. SECTION 607.3.2 |
| | 56) SHT P6.02 FUEL TANK ROOM, CONTAIN- |
| | MENT IN CASE OF SPILLAGE? |
| | 57) SEPARATE PLANS & PERMIT REQUIRED FOR |
| | POOL AND POOL EQUIPMENT ROOM. PLEASE |
| | ROUTE PLANS TO PALM BEACH HEALTH UNIT |
| | DIVISION OF ENVIRONMENTAL HEALTH 901 |
| | EVERNIA ST WPB 33401 (561) 355-3018 |
| | 58) BACKFLOW REQUIRED FOR SWIMMING POOL |
| | WATER SERVICE SUPPLY LINE. BACKFLOW RE- |
| | QUIRED FOR IRRIGATION. |
| | 59) PLEASE PROVIDE DETAILS FOR POOL PUMP |
| | AND EQUIPMENT ROOM PER SECTION 424.1.5 |
| | AND ALL SUBSECTIONS. |
| | |
| | LOOK FOR COMMENTS BY THE OTHER PLAN |
| | REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| | ON THE APPLICATION, PLANS, OR ATTACHED |
| | SEPARATELY. WHEN RESUBMITTING PLANS |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | |
| | |
| | |
| | |
| | |
| | COOPERATION. |
| | |