| 2003-03-10 00:00:00 | DENIED: |
| | |
| | 1.PLAN SHEET M1.02, INDICATES SMOKE |
| | REMOVAL DUCT TERMINATION.CLARIFY |
| | DISTANCE TO ANY FRESH AIR OPENINGS, I.E. |
| | DOORS, WINDOWS, O.A. INTAKES. |
| | |
| | 2.PLAN SHEET M2.01, EXHAUST DUCT |
| | PASSING FROM CORRIDOR, BY STAIRS, THRU |
| | TO BREEZEWAY & UP TO MEZZANINE - NO |
| | DAMPERS INDICATED. |
| | |
| | 3.PLAN SHEET M2.02, AHU R/A DUCT |
| | PENETRATES CORRIDOR WALL LEAVING AHU |
| | CLOSET & AGAIN GOING BACK INTO THE FOYER |
| | OF UNIT 16L & 18L, NO FIRE/SMOKE DAMPERS |
| | INDICATED. |
| | |
| | 4.SHAFTS THAT ENCLOSE ENVIRONMENTAL |
| | AIR DUCTS SHALL NOT ENCLOSE ANY OTHER |
| | TYPE OF DUCTS (NFPA 90A 3-3.4.3).PLAN |
| | SHEET M2.02 SHOW SUPPLY AIR DUCTS IN THE |
| | SAME SHAFT AS EXHAUST DUCT, PLEASE |
| | CLARIFY. |
| | |
| | 5.PLAN SHEET M2.03, DUCT CONTINUES UP |
| | TO MEZZANINE NO DUCT SIZE INDICATED. |
| | |
| | 6.M2.08, O.A. DUCT TO WCACU-L.2-2, |
| | RATED WALL, NO FIRE DAMPER INDICATED. |
| | |
| | 7.M2.08 O.A. DUCT, SUPPLY DUCT |
| | PENETRATES RATED WALL, PLEASE CLARIFY. |
| | |
| | 8.SEE COMMENT # 3 FOR THE FOLLOWING |
| | UNITS: 11L, 27, 28, 29, B4, 16L. |
| | |
| | 9.PLAN SHEET P2.45 INDICATES A FLOOR |
| | DRAIN IN THE PARKING GARAGE EXHAUST |
| | SHAFT.EXPLAIN HOW THIS IS GOING TO |
| | WORK. |
| | |