| 2003-03-14 00:00:00 | 1) UNABLE TO LOCATE WRITTEN COMMENTS |
| | FOR PREVIOUS PLAN REVIEW NOTES |
| | PROVIDED BY FIRE RESCUE. |
| | |
| | 2) PLEASE PROVIDE MORE INFORMATION WITH |
| | REGARDS TO GLASS IN LOBBY DOORS THAT |
| | ARE PROTECTED WITH A SPRINKLER HEAD ON |
| | EACH SIDE OF THE GLASS. WATER CURTAINS |
| | ARE NOT DESIGNED TO PROTECT DOORS. |
| | PROVIDE RECOGNIZED TEST DATA. |
| | |
| | 3) ALL EXIT STAIR DOORS SHALL HAVE |
| | TACTILE SIGNAGE. |
| | |
| | 4) ALL EXIT STAIRS THAT TERMINATE INTO |
| | EXIT PASSAGEWAYS SHALL HAVE THE SAME |
| | FIRE PROTECTION RATING AS THE STAIR. |
| | PLEASE DEMONSTRATE THIS. |
| | |
| | 5) THE ORIGNIAL PLANS PROPOSED A 1000 |
| | GPM FIRE PUMP. THIS INFORMATION DOES |
| | NOT APPEAR TO BE CORRECT. ALL REQUIRED |
| | STAIRS FOR THE BUILDING SHALL HAVE |
| | STANDPIPE CONNECTIONS. IF EIGHT STAIRS |
| | ARE REQUIRED, THEN IN REALITY A 1000 |
| | GPM FIRE PUMP IS NOT LARGE ENOUGH. |
| | PLEASE ADVISE. |
| | |
| | 6) PLEASE EXPLAIN GATES AND CARD |
| | READERS AND HOW DO THEY EFFECT EXITING. |
| | |
| | 7) PLEASE EXPLAIN OPEN UNPROTECTED |
| | STAIRS. |
| | |
| | 8) STAIR # 10 IS NOT IDENTIFIED ON |
| | STAIR TERMINATION POINT BOX. |
| | |
| | 9) STAIR # 9 IS NOT IDENTIFIED ON |
| | STAIR TERMINATION POINT BOX. |
| | |
| | 10) PLEASE PROVIDE FIRE RATINGS FOR |
| | STAIR # 10. |
| | |
| | 11) STAIR # 5 APPEARS TO BE OPEN. |
| | PLEASE EXPLAIN RATIONALE. |
| | |
| | 12) HOW DO YOU DIRECT PERSONS VIA |
| | STAIRS ACROSS AREAS OF PARKING TO |
| | REACH ENCLOSED EXIT STAIRS. |
| | |
| | 13) HOW ARE PATHS OF TRAVEL DEFINED ON |
| | THE LANAI LEVEL. |
| | |
| | 14) PLEASE EXPLAIN NOTES ON PAGE LS-109 |
| | "GATE AUTOMATICALLY UNLOCKS IN FIRE |
| | MODE PER FBC 1012.7. |
| | |
| | 15) MORE DETAILS NEEDED ON ROUND FOAM |
| | COLUMNS SHOWN ON A3.01. |
| | |
| | 16) THE KNOX-BOX IS NOTED TO BE |
| | INSTALLED ON THE INSIDE OF THE BUILDING. |
| | KNOX-BOXES ARE TO BE INSTALLED ON |
| | THE EXTERIOR OF THE BUILDING. |
| | |
| | 17) EXIT ACESS ON MAIN ROOF LEVEL PLAN |
| | NOTED THRU DEDICATED AREA FOR |
| | LEASABLE SPACE. |
| | |
| | 18) EXPANDED POLYSTYRENE NOTED IN |
| | BUILDING SECTIONS 3 & 3A. |
| | |
| | 19) PLEASE PROVIDE INFO ON 1" INSULATION |
| | AROUND TRASH CHUTE. |
| | |
| | 20) EXIT SIGN MISSING IN CORRIDOR, |
| | GROUND LEVEL LOBBY AREA ON PAGE E2.01 |
| | TO DIRECT PERSONS TO EXIT BEYOND STAIR |
| | ENCLOSURE. |
| | |
| | 21) NO EXIT SIGN SHOWN ON GROUND LEVEL, |
| | LOBBY AREA II ON PAGE E2.02. |
| | |
| | 22) NO EXIT SIGNS SHOWN ON GROUND LEVEL, |
| | LOBBY AREA III ON E2.03. |
| | |
| | 23) PLEASE EXPLAIN WHY EXITING ON LS 102 |
| | GOES THRU BICYCLE STORAGE AND WHAT |
| | CODE REFERENCE ALLOWS THIS. |
| | |
| | 24) ONLY ONE EXIT SIGN SHOWN ON GROUND |
| | LEVEL LOBBY AREA IV. |
| | |
| | 25) IT APPEARS THAT DOOR FROM STAIR # 10 |
| | OPENS INTO TENANT STORAGE ROOM A ON |
| | PAGE E2.10. |
| | |
| | 26) COULD NOT LOCATE ANY EXIT SIGNS |
| | IN CORRIDOR ON PAGE E2.12. |
| | |
| | 27) ONLY ONE EXIT SIGN SHOWN IN CORRIDOR |
| | ON PAGE E2.13. |
| | |
| | 28) NO DIRECTIONAL EXIT SIGNS SHOWN |
| | IN CORRIDOR, TOWER 6TH LEVEL, AREA I |
| | PAGE E2.19. |
| | |
| | 29) NO EXIT SIGNS SHOWN IN CORRIDOR |
| | ON PAGE E2.23. |
| | |
| | 30) NO EXIT SIGNS SHOWN IN FITNESS |
| | AREA/YOGA AEROBICS ROOM. |
| | |
| | 31) EMERGENCY GENERATOR DETAIL INDICATES |
| | A SUB-BASE FUEL TANK. ROOM IF |
| | CONTAINING FUEL IS TO BE PROPERLY |
| | FIRE RATED. |
| | |
| | 32) SMOKE DETECTORS ARE REQUIRED IN |
| | EVERY MECHANICAL,ELECTRICAL,TRANSFORMER, |
| | AND TELEPHONE EQUIPMENT PER 412.2. |
| | |
| | 33) ONLY ONE EXIT SIGN SHOWN ON PAGE |
| | E2.49. |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |