| Date |
Text |
| 2003-03-07 00:00:00 | PAID PLAN REVIEW, NOT A PERMIT |
| | APPLICATION. |
| | |
| | AT TIME OF PERMIT APPLICATION, THE |
| | ENERGY CODE CALCULATIONS ARE REQUIRED |
| | TO BE SIGNED, DATED AND SEALED BY THE |
| | PREPARER. FBC 13-103.1 |
| | |
| | COMPLETE SPECIFICATIONS HAVE NOT BEEN |
| | PROVIDED, THEY WILL BE NECESSARY FOR |
| | THE PERMIT APPLICATION.SEE FBC 104.2.1 |
| | |
| | CONCURRENT WITH THE PERMIT APPLICATION |
| | COMPLIANCE WITH FBC 1803.1.3 AND 1803.2 |
| | MUST BE DEMONSTRATED. |
| | |
| | ITEM #6 UNDER BUILDING CODE INFO ON |
| | SHEET LS 1.00 DECLARES FIRE RATING |
| | REDUCTIONS APPLIED.SEE FBC TABLE 600 |
| | FOOTNOTE (L) FORTHE LIMITATIONS. |
| | EXTERIOR WALLS, SHAFT ENCLOSURES AND |
| | OCCUPANCY SEPARATIONS ARE NOT INCLUDED. |
| | |
| | SHEET LS NOTE 9 SPEAKS TO GLASS IN DOORS |
| | HAVING A SPRINKLER ON EACH SIDE. |
| | OPENING PROTECTIVES MUST COMPLY WITH |
| | FBC 705. |
| | |
| | NOTE 8 ON LS 1.00 IMPLIES AND IMPROPER |
| | APPLICATION OF FBC TABLE 600. |
| | HORIZONTAL MEASUREMENTS ARE FROM THE |
| | WALL PLANE AND VERTICAL MEASUREMENTS |
| | ARE PER FLOOR, FROM FINISH FLOOR TO |
| | CEILING ABOVE. |
| | |
| | NOTE 18 SPEAKS TO FOAM MOLDINGS. |
| | ARCHITECTURAL TRIM IS REQUIRED TO BE |
| | NON-COMBUSTIBLE OR FRT WOOD.SEE FBC |
| | F102.2.7 AS AMENDED BY THE CITY AND FBC |
| | 1404. |
| | |
| | SEVERAL OF THE MEZZANINE UNITS SHOW A |
| | TRAVEL DISTANCE >75'. FBC 1005.7.1 |
| | REQUIRES TWO MEANS OF EGRESS COMPLYING |
| | WITH FBC 1004.1.4. |
| | |
| | THE STAIRS SHOWN AS #5, #7 AND #10 DO |
| | NOT COMPLY WITH FBC 1006.1.1 AND FBC |
| | 412.11 #5. |
| | |
| | SHEET A11.05. IF THE HC PARKING SPACES |
| | SERVICE THE GROUP "B" LIVE WORK LOFT |
| | THEY MUST BE 12' WIDE IN ACCORDANCE |
| | WITH FBC 11-4.6 INCLUDING THE 98" |
| | VERTICAL CLEARANCE. |
| | |
| | SHEET A6.05 SHOWS POLYSTYRENE TO VE |
| | USEDFOR EXTERIOR TRIM.THIS IS |
| | PROHIBITED BY FBC F102.2.7 (AMENDED) |
| | FBC 1404 |
| | |
| | SHEET A11.01, SHOW A SPECIFIC FRAMING |
| | AND FASTENING DETAIL FOR THE SUSPENDED |
| | GYP BOARD CEILINGS. FBC 104.2. |
| | |
| | THE WALL SHOWN AS W19 ON SHEET S-32 IS |
| | ABERING WALL AND IS REQUIRED TO BE FIRE |
| | RATED.SEE FBC TABLE 600. |
| | |
| | THE WIND TUNNEL TEST REPORT EXCLUDES |
| | THE ROOF TILE FROM ITS FINDINGS. |
| | PROVIDE THE NECESSARY INFORMATION IN |
| | ACCORDANCE WITH FBC 104.2.1.1. |