| 2004-08-16 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | |
| | 1) NUMEROUS SHEETS SHOW NOT CHANGES FROM |
| | THE LAST REVISION OR SINCE THE PLANS |
| | WERE STAMPED. PLEASE DELETE ALL SHEETS |
| | THAT HAVE NOT REVISION TO REVIEW. SECT- |
| | ION 104.2.1 |
| | 2) SHTS P2.01 & P3.13 RISER DIAGRAM DOES |
| | NOT REFLECT FLOOR PLAN. RISERS DOWN- |
| | STREAM OF 5" @ 302 FU SHOW 3" 4FU THEN |
| | 2" 2FU ON FLOOR PLAN BUT RISER SHOWS THE |
| | 2" 2FU & 3" 4FU IN REVERSE ORDER. THIS |
| | IS SHOWN AT 3 DIFFERENT AREAS. PLEASE |
| | CORRELATE PLANS. SECTION 104.2.1 |
| | 3) SHT P301 AIR CHAMBERS ARE NOT APPROV- |
| | ED IN MEN'S AND WOMEN'S BATHROOMS, AND |
| | A WATER HAMMER ARRESTOR IS REQUIRED AT |
| | THE DISH WASHER ON RISER FOR MEN'S BATH- |
| | ROOM. SECTION 604.9 |
| | 4) SHT P3.05 UNIT 25 WATER RISER DOES |
| | NOT REFLECT THE FLOOR PLAN ON SHT P2.16 |
| | NO WATER SUPPLY SHOWN TO SHOWER. |
| | 5) SHT P3.05 UNITS 1, 25, 28, & 38 WATER |
| | RISER DIAGRAMS. WATER HAMMER ARRESTORS |
| | ARE REQUIRED AT THE DISH WASHER & ICE |
| | MAKER IN THE REFRIG. SECTION 604.9 |
| | 6) SHT P3.18 RISER 27/30 2ND/4TH FLOOR |
| | ISLAND VENT NOT APPROVED. VENT LINE |
| | SHOWN TIED BACK INTO THE VENT FROM THE |
| | ISLAND VENT IS A HORIZONTAL DRY VENT AND |
| | NOT APPROVED. SECTION 905.3 |
| | |
| | REVIEW BY KEN STEVENS |