02040459 |
|
| Review Stop |
P |
| Sequence Number |
12 |
|
| Notes |
| Date |
Text |
| 2004-07-15 00:00:00 | DENIED | | | REFERENCE: FBC-2001 CHAPTER 14 | | | FBC-2001 PLUMBING | | | | | | | | | 1) SECTION 1 AIR CHAMBERS ARE NOT APPRO- | | | VED. DELETE FROM SUBMITTAL. SEC 604.9 | | | 2) SECTION 2 HANGERS AND SUPPORTS. SUB- | | | MITTAL INDICATES THAT THEY ARE UL LISTED | | | PROVIDE UL LISTING IDENTIFICATION NUMBER | | | FOR VERIFICATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|