| 2004-08-12 00:00:00 | ************ UNSAT ******************* |
| | |
| | 1)NOTE: PLEASE ONLY SUBMIT SHEETS WHICH |
| | ARE BEING REVISED/NEEDING REVIEW. |
| | PLEASE SEE THERE ARE MANY SHEETS THAT |
| | HAVE ALREADY BEEN SUBMITTED FOR REVIEW |
| | AND HAVE BEEN STAMPED ON PREVIOUS REVIEW |
| | 'S. |
| | |
| | 2)NOTE: PLEASE SEE EGRESS LTS/CONTROLS |
| | HAVE NOW BEEN REMOVED FROM UNIT ON FIRST |
| | FLR WHICH EXIT TO STREET. NEC 210.70 |
| | LS 101 5-8. |
| | PLEASE SEE THAT SPEACIAL PERMISSION |
| | SHALL BE REQUIRED FOR REMOVAL OF THE |
| | REQUIRED EGRESS LTS/CONTROL PER CODES |
| | ABOVE. |
| | PLEASE ADDRESS THE ABOVE. |
| | PLEASE CLARIFY WHAT WILL EGRESS LT BE? |
| | ETC |
| | |
| | 3)NOTE: PLEASE SEE SOME UNITS ARE MISS- |
| | -ING RECEPTS REQUIRED PER 210.52C3,C5 |
| | PLEASE SEE 2.32 UNIT "M" KIT PENINSULAR. |
| | PLEASE SEE 2.33,2.34 UNIT "O1" FOR SAME. |
| | |
| | 4)NOTE: PLEASE KNOW, LIGHTNING PROTECT- |
| | -ION NOW SUBMITTED TO MEET NFPA-780 IS |
| | OK. |
| | IF INSTALLED AND CERITIFIED BYA |
| | SUB-CONTRACTOR, A SEPARATE WILL BE |
| | REQUIRED. |
| | |
| | PLEASE BE SURE TO SEE POSSIBLE COMMENTS |
| | FROM OTHER REVIEWERS WHICH MAY HAVE AN |
| | AFFECT ON ELECTRICAL PLANS. |
| | |
| | ***** PLEASE REMOVE ALL OLD/VOIDED SHEET |
| | -S AND ONLY INSERT NEW SHEETS FOR REVIEW |
| | AND STAMPING. PLEASE REMOVE ALL SHEETS |
| | WHICH DO HAVE NEW REVISIONS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |