| 2002-05-10 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | |
| | 1) PLANS ARE NOT COMPLETE FOR SUFFICIENT |
| | REVIEW. MORE INFORMATION IS REQUIRED FOR |
| | COMPLETE REVIEW. |
| | 2) SHT P1.01 OIL INTERCEPTORS, PLEASE |
| | CONTACT RODNEY COMPO ENVIRONMENTAL COM- |
| | PLIANCE FOR SIZE OF OIL INTERCEPTORS |
| | (561) 837-4074.(SHT P1.05 ALSO) |
| | 3) SHT P1.05 NOT SANITARY SHOWN FOR |
| | POWDER ROOM. |
| | 4) SHT P1.07 BATH B2 NO SANITARY SHOWN |
| | TO WATER CLOSET. |
| | 5) SHT P1.26 M/BATH UNIT K NO SANT TO |
| | TUB. |
| | 6) SHT P1.28 SHOWS STEAM SAUNA IN MENS |
| | ROOM AND URNAL IN WOMENS ROOM ??? |
| | 7) SHT P1.40 BATHROOM B2 BY STAIR #4 TUB |
| | NOT VENTED PROPERLY |
| | 8) SHT P1.42 RISER #5 W/C NOT VENTED. |
| | 9) SHT UNIT R WASH MACHINE SHALL NOT |
| | DRAIN INTO BATHROOM GROUP. |
| | 10) SHT P1/47 TUB NOT VENTED UNIT T |
| | 11) SHT P1.56 RISERS ARE INCOMPLETE. |
| | PLEASE IDENTIFY EACH RISER. RELIEF VENT |
| | NOT SHOWN ON RISERS |
| | 12) PLEASE SUBMIT RISER DIAGRAMS FOR |
| | STORM, WATER, CONDENSATE, RELIEF VALVE - |
| | (P/T) DISCHARGE, & EMERGENCY PAN DRAIN. |
| | ALSO GIVE A COMPLETE RISER DIAGRAM ISO- |
| | METRIC SHOWING COMPLETE SYSTEMS WITH |
| | HORIZONTAL PIPING, PIPE SIZE FIXTURE UN- |
| | IT LOADS AS THEY ACCUMULATE AT EACH RIS- |
| | ER ALL THE WAY OUT OF BLDG. |
| | 13) SHOW ALL OFFSETS FOR EACH SANITARY R |
| | ISERS AND INDICATE IF VERITCAL OR HORIZ- |
| | ONTAL OFFSETS. |
| | 14) VENTS NOT SHOWN THRU ROOF. |
| | 15) SHT 1.64 LANAI ROOF - WHAT IS THE |
| | DESIGNATION PR REFER TO? NOT ALL PIPES |
| | ARE SIZED. |
| | 16) SHT A1.05 TRANSFORMER VAULT, IS SUMP |
| | TO BE PIPED OR JUST FOR CONTAINMENT OF |
| | OILS IN CASE OF EMERGENCY? |
| | 17) SHT A1.05 GARAGE EXHAUST AND AIR |
| | SUPPLY FLOOR DRAINS, TO STORM? WILL FIRE |
| | AND DOMESTIC PUMP RMS HAVE FLOOR DRAINS? |
| | 18) SHT A1.05 FUEL TANK ROOM, CONTAIN- |
| | MENT IN CASE OF SPILLAGE? |
| | 19) PLEASE SUBMIT CALCULATIONS FOR ALL |
| | PRIMARY AND SECONDARY ROOF DRAINS. ADD |
| | ALL AREAS OF ROOF THAT DRAIN FROM ABOVE |
| | AND 1/2 ALL AREA OF ALL VERTICAL WALLS. |
| | SHOW LOCATION OF ALL SECONDARY ROOF |
| | DRAINS. CALCULATE PER FBC PLMB SEC 1106 |
| | & 1107, TABLES 1106.2, & 1106.3, FIGURE |
| | 1106.1. |
| | 20) PLEASE INDICATE MATERIALS USED FOR |
| | ALL PLUMBING SYSTEMS. |
| | 21) PLEASE SHOW BACKFLOWS REQUIRED FOR |
| | MAKE UP WATER TO COOLING TOWERS, SWIMM- |
| | ING POOL, & IRRIGATION. PLEASE INDICATE |
| | MANUFACTURE AND MODEL NUMBER, AND LOCAT- |
| | ION OF EACH. |
| | 22) SEPARATE PLANS AND PERMIT REQUIRED |
| | FOR POOL, & POOL EQUIPMENT ROOM. PLEASE |
| | ROUTE PLANS TO PALM BEACH HEALTH UNIT |
| | DIVISION OF ENVIRONMENTAL HEALTH 901 |
| | EVERNIA STREET, WPB FL 33401 (561) 355- |
| | 3018. |
| | 23) PLEASE SUBMIT DETAILS FOR SAUNA AND |
| | STEAM ROOMS |
| | 24) PLEASE SUBMIT WATER HEATER DETAILS. |
| | PROVIDE INFORMATION FOR SEC 504.7.1, THE |
| | DISCHARGE PIPE SHALL NOT HAVE ANY TRAPP- |
| | ED SECTIONS AND SHALL HAVE A VISIBLE AIR |
| | GAP OR AIR GAP FITTING LOCATED IN THE |
| | SAME ROOM AS HEATER. SUBMIT INFO FOR |
| | THERMAL EXPANSION CONTROL, 607.3 |
| | 25) SHT A8.22 PLEASE SHOW CLEAR FLOOR |
| | SPACE FOR URNAL. (30"X48" MINIMUM) |
| | 26) SHTS A8.33/A8.34 UNIT Q, FIREPLACE |
| | PLEASE SUBMIT DETAILS. SHOW EXHAUST DUCT |
| | IS THIS A GAS FIREPLACE? |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT 8377 |