| | 1.PLAN SHEET M1.06 - PLEASE CLARIFY |
| | DUCTS APPEAR TO BE IN ONE SHAFT.NOTE |
| | 11 DRYER EXHAUST, NOTE 12 TRANSFER |
| | GRILLE AND THE 3RD IS NOT IDENTIFIED |
| | BUT APPEARS TO BE OUTSIDE AIR.AS PER |
| | 2001 FBC(M) 603.8, CAVITIES IN FRAMED |
| | SPACES SHALL NOT BE USED TO DELIVER |
| | AIR FROM OR RETURN AIR TO CONDITIONING |
| | SYSTEM UNLESS THEY CONTAIN AN AIR DUCT |
| | INSERT INSULATED IN ACCORDANCE WITH |
| | TABLE 4-10 OR 6-10 CHAPTER 13 OF THE |
| | FBC. |
| | |
| | 2.SHAFTS THAT CONSTITUTE AIR DUCTS OR |
| | ENCLOSE AIR DUCTS USED FOR ENVIRONMENTAL |
| | AIR SHALL NOT ENCLOSE: EXHAUST DUCTS |
| | USED FOR THE REMOVAL OF SMIKE & GREASE |
| | LADEN VAPORS FROM COOKING EQUIPMENT, |
| | DUCTS USED FOR CONVEYING VAPOR OR DUST, |
| | REFUSE & LINEN CHUTES, PIPING OR |
| | COMBUSTIBLE STORAGE. |
| | |
| | 3.M1.07 CLARIFY DUCTWORK DOWN AT STAIR |
| | #2.NO FIRE DAMPERS ARE INDICATED. |
| | DUCTS SHALL NOT RUN IN THE STAIRWELL. |
| | |
| | 4.M1.08 DUCTS TO THE CORRIDOR, FIRE |
| | DAMPERS ARE NOT INDICATED. 2001 FBC(M) |
| | 607.6, SPECIFIC LOCATION & INSTALLATION |
| | DETAILS OF EACH FIRE DOOR, CEILING |
| | DAMPER AND FIRE & OR SMOKE DAMPERS |
| | SHALL BE SHOWN & PROPERLY IDENTIFIED ON |
| | PLANS. |
| | |
| | 5.PLAN SHEET 4.11 DETAIL FOR GARAGE |
| | EXHAUST MUST HAVE A POSITIVE CONNECTION |
| | BETWEEN GRILLE & INTAKE TO FAN. |
| | |
| | 6.OVERFLOW PROTECTION REQUIRED AS PER |
| | 2001 FBC(M) 307.2.3 & 307.2.4. |
| | |
| | 7.PROVIDE DETAILS FOR THE GENERATOR |
| | EXHAUST.INDICATE TERMINATION IN |
| | COMPLIANCE WITH NFPA 110 5-10. |
| | |
| | 8.PROVIDE STAIRWELL ELEVATION |
| | INDICATING LOCATION OF FAN, LOUVERS. |
| | |
| | 9.INDICATE HOW DUCTWORK IS TO BE |
| | ACCESSED UNDER THE POOL AREA.WILL |
| | DUCTWORK HAVE ANY PROTECTION FROM |
| | MOISTURE, ELEMENTS OR DAMAGE? |
| | |
| | 10. PROVIDE SEQUENCE OF OPERATION. |
| | |
| | 11. PROVIDE TEST CRITERIA FOR SMOKE |
| | EVAC/CONTROL. |
| | |
| | 12. OUTSIDE AIR CALCULATIONS SHALL |
| | PROVIDE COMPLIANCE WITH 402.2 (4% OF |
| | THE FLOOR AREA BDING VENTILATED) OR |
| | TABLE 403.3 (MECHANICAL VENTILATION NOT |
| | INFILTRATION). |
| | |
| | 13. AS PER 2001 FBC(M) 602.2.1, |
| | MATERIALS EXPOSED WITHIN PLENUMS SHALL |
| | BE NONCOMBUSTIBLE. |
| | |
| | |