| 2002-05-07 00:00:00 | 1) ADDRESS FOR BUILDING REQUIRED. A |
| | MINIMUM OF SIX INCH NUMERALS REQUIRED. |
| | |
| | 2) TEMPORARY STANDPIPES ARE REQUIRED |
| | WHEN THE BUILDING REACHES THREE STORIES |
| | OR THIRTY FEET IN HEIGHT. |
| | |
| | 3) STAIRS ARE TO BE KEPT UP WITH |
| | CONSTRUCTION. |
| | |
| | 4) WET FIRE HYDRANTS ARE REQUIRED PRIOR |
| | TO, DURING AND AFTER CONSTRUCTION. |
| | |
| | 5) PLEASE BE ADVISED THAT THIS BUILDING |
| | IS LOCATED WITHIN THE CITY FIRE LIMITS. |
| | CERTAIN RESTRICTIONS APPLY. PLEASE |
| | SEE CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FLORIDA BUILDING CODE. |
| | |
| | 6) PLEASE PROVIDE PRODUCT APPROVALS FOR |
| | THE WON ELEVATOR DOORS. |
| | |
| | 7) PLEASE INDICATE INTERIOR FINISH |
| | CLASSIFICATION INFORMATION FOR WALLS |
| | AND CEILINGS OF THE BUILDING. |
| | |
| | 8) CEDER TRELLISES NOTED ON LOWER ROOF |
| | POOL DECK. AGAIN, THE BUILDING IS |
| | LOCATED WITHIN THE CITY FIRE LIMITS |
| | CERTAIN RESTRICTIONS APPLY. |
| | |
| | 9) EIFS NOTED ON BUILDING ELEVATIONS. |
| | PLEASE SEE LOCAL AMENDMENTS REGARDING |
| | ARCHITECTURAL TRIM IN THE FIRE LIMITS. |
| | |
| | 10) THE USE OF PROPANE BARBECUE GRILLS |
| | ABOVE THE FIRST FLOOR ON THE BALCONIES |
| | ARE PROHIBITED. |
| | |
| | 11) ALL SHAFTWAYS THAT ARE ACCESSIBLE |
| | TO THE FIRE RESCUE DEPARTMENT WHICH |
| | PERSONS CAN FALL INTO ARE TO BE MARKED |
| | "SHAFTWAY IN RED LETTERS, SIX INCHES |
| | HIGH ON A WHITE BACKGROUND" PER NFPA 1. |
| | |
| | 12) A KNOX-BOX WILL BE REQUIRED FOR |
| | FIRE RESCUE ACCESS. |
| | |
| | 13) ALL STAIRS ARE TO BE PROVIDED WITH |
| | SIGNAGE TO INDICATE THE STAIR, THE |
| | STORY, THE TERMINUS TOP AND BOTTOM. |
| | |
| | 14) ALL CANVAS CANOPIES ARE TO BE FIRE |
| | RETARDENT. |
| | |
| | 15) NO COMBUSTIBLE MATERIALS ARE ALLOWED |
| | WITHIN THE RETURN AIR PLENUMS. |
| | |
| | 16) PLEASE INDICATE THAT ALL OF THE |
| | PRESCRIPTIVE CODE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, SECTION 412.4.3 |
| | "FIRE COMMAND STATIONS" ARE BEING MET. |
| | |
| | 17) SITE PLAN INDICATES A SIX INCH FIRE |
| | LINE ENTERING THE BUILDING. ON ANOTHER |
| | SHEET, IT DISPLAYS AN EIGHT INCH LINE. |
| | PLEASE BE ADVISED THAT AN EIGHT INCH |
| | LINE IS THE MINIMUM THAT WILL BE ALLOWED |
| | FOR A 1000 GPM FIRE PUMP THAT HAS BEEN |
| | PROPOSED. |
| | |
| | 18) SITE PLAN DOES NOT SHOW FIRE MAIN |
| | SIZE ON OKEECHOBEE BOULEVARD. |
| | |
| | 19) THE FIRE LINE SHOWN RUNNING UNDER |
| | THE BUILDING'S FOUNDATION IS NOT ALLOWED |
| | BY THE CODE UNLESS NO OTHER ALTERNATIVE |
| | IS AVAILABLE. |
| | |
| | 20) NO DETAILS PROVIDED FOR PRESSURE |
| | RELIEF DEVICES PROPOSED. |
| | |
| | 21) PLEASE VERIFY THAT THE CENTRAL FIRE |
| | SPRINKLER HEADS THAT ARE PLANNED FOR |
| | USE ARE NOT ON THE VOLUNTARY RECALL |
| | LIST, PLEASE SEE WWW. |
| | SPRINKLERREPLACEMENT.COM. |
| | |
| | 22) FIRE SPRINKLER PLANS DO NOT NOTE |
| | THAT PRESSURE TESTING IS REQUIRED FOR |
| | ALL UNDERGROUND FIRE MAINS AND ABOVE |
| | GROUND FIRE SPRINKLER PIPING. |
| | |
| | 23) AREAS OF THE FIRE SPRINKLER PLANS |
| | ARE MISSING FIRE SPRINKLER PROTECTION. |
| | |
| | 24) PLEASE EXPLAIN EXITING RATIONALE |
| | FROM THE PARKING GARAGE. |
| | |
| | 25) PLEASE INDICATE ON THE ELECTRICAL |
| | PLANS THAT ALL SMOKE DETECTORS ARE TO |
| | BE INSTALLED A MINIMUM OF THREE FEET |
| | FROM AIR CONDITIONER DIFFUSERS. |
| | |
| | 26) PLEASE EXPLAIN PURPOSE OF |
| | DIRECTIONAL EXIT SIGN NEAR OPEN STAIRWAY |
| | ACCROSS FROM TOWNHOUSE SIX IN CORRDIOR. |
| | |
| | 27) MANUAL PULL STATION AND HORN STROBE |
| | NOTED IN MIDDLE OF STAIRWAY ON PAGE |
| | E1.08. |
| | |
| | 28) PLEASE EXPLAIN LEDGES. |
| | |
| | 29) IT WAS NOTED THAT SMOKE DETECTORS |
| | ARE SHOWN IN THE CORRIDORS OF THE |
| | BUILDING. PLEASE BE ADVISED THAT SPACING |
| | OF THESE DETECTORS ARE NOT TO EXCEED |
| | CODE REQUIREMENTS. PLEASE CHECK THE |
| | SPACING OF THESE DEVICES. |
| | |
| | 30) NO ILLUMINATED EXIT SIGNS LOCATED |
| | FOR THE SECOND LEVEL PARKING AREA. |
| | |
| | 31) FIRE ALARM NOTES SECTION NUMBER |
| | TWELVE INDICATES THAT THE BUILDING WILL |
| | BE CONSIDERED TWO SEPARATE BUILDINGS |
| | ABOVE THE FIFTH FLOOR. PLEASE EXPLAIN |
| | RATIONALE. |
| | |
| | 32) PLEASE INDICATE WHAT THE VOICE |
| | EVACUATION PORTION OF THE FIRE ALARM |
| | SYSTEM WILL INDICATE TO PERSONS WITHIN |
| | THE BUILDING. |
| | |
| | 33) THE MECHANICAL PLANS MAKE REFERENCE |
| | TO SECTION 412.5. HOW ARE THE OPERABLE |
| | WINDOWS GOING TO BE IDENTIFIED. |
| | |
| | 34) PLEASE INDICATE THAT THE FUEL |
| | SUPPLY TO OPERATE EMERGENCY POWER |
| | IS AMPLE TO SUPPLY A MINIMUM OF TWO |
| | HOURS PER FBC 412.7.1.2. |
| | |
| | 35) EMERGENCY LIGHTING REQUIRED FOR |
| | FIRE PUMP ROOM. |
| | |
| | 36) THE PLANS SUBMITTED APPEAR TO BE |
| | INCOMPLETE. |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| | 659-8096,EXT.8497 |
| | 835-2910 |