| 2002-05-06 00:00:00 | *************** UNSAT ***************** |
| | |
| | PLEASE NOTE THAT PLANS ARE NOT COMPLETE |
| | FOR SUFFICIENT REVIEW. |
| | PLEASE ALSO NOTE THAT SOME OF THE |
| | NOTES ARE SET AS TYPICAL FOR MANY UNITS. |
| | |
| | |
| | 1)NOTE: PLEASE NOTE,E1.02 NOTE SAYS TO |
| | SEE E0.00 FOR ELEC RM DETAIL? PLEASE |
| | NOTE ELEC RM IS NOTE SHOWN ON THAT PAGE. |
| | |
| | |
| | 2)NOTE: PLEASE NOTE THAT SOME NOTE ON |
| | E1.01,1.02 ETC MENTION TO SEE E1.05 FOR |
| | TYP UNITS AND THOSE UNITS ARE NOT SHOWN |
| | ON OTHER SHEET.? PLEASE NOTE THAT THIS |
| | IS TYP FOR OTHER SHEETS AS WELL. |
| | |
| | 3)NOTE: PLEASE NOTE E1.05 ,SOME UNITS |
| | SHOWING TWO PANELS? (TH-1,TH-2 ETC ) |
| | PLEASE CLARIFY. MISPRINT? |
| | |
| | 4)NOTE: PLEASE NOTE THAT SOME UNIT IN |
| | THE BEGINING PART OF THE SETS ARE NOT |
| | SHOWING CATV. PLEASE NOTE IF CATV IS |
| | GOING TO BE THOSE UNITS, PLEASE REVISE |
| | AND SHOW. |
| | |
| | 5)NOTE: PLEASE NOTE TYPICAL OF ALL UNITS |
| | PLEASE SHOW/CLARIFY GFI/GFI PROTECTION |
| | FOR ALL JACUZZI/SPA UNITS. 680-42 |
| | |
| | 6)NOTE: PLEASE NOTE MISSING HALLWAY REC |
| | 210-52H. PLEASE NOTE MISSING INSOME UNIT |
| | -S. |
| | |
| | 7)NOTE: PLEASE NOTE TYPICAL FOR MANY |
| | UNITS, 2` 6 ` RULE FOR RECEPT SPACING |
| | PER 210-52. PLEASE NOTE SOME UNITS ARE |
| | MISSING MORETHAN OTHERS. |
| | |
| | 8)NOTE: PLEASE NOTE E1.20 PANEL SHOWN |
| | IN THE MIDDLE OF THE ROOM WITH OTHER |
| | EQUIPMENT?? PLEASE CLARIFY. |
| | |
| | 9)NOTE: PLEASE NOTE THAT ALL SMOKE |
| | DETECTORS ARE TO BE A MIN OF 3' FROM |
| | BATHS RMS AND KITCHENS. NFPA-72 2-5.2.1. |
| | 6. |
| | |
| | 10)NOTE:PLEASE NOTE RECEPT SPACING FOR |
| | ALLKITCHENS COUNTERSPACES 210-52C-1 |
| | PLEASE NOTE FOR 12", 24" ETC. |
| | |
| | 11)NOTE: PLEASE NOTE PENINSULAR RECEPT |
| | SPACINGPER 210-52C-3. PLEASE NOTE THAT |
| | ANY INTERUPTION OF CONTINUOUS SPACE |
| | REQ`SADDTIONAL RECEPTS. (SINKS) |
| | * PLEASE NOTE MANY UNITS ARE MISSING |
| | RECEPTS PER 210-52C 1,2,3,4,5*** |
| | |
| | 12)NOTE: PLEASE NOTE E1.28 UNIT B2 SAYS |
| | SEE SIMULAR UNIT ON E1.29? PLEASE NOTE |
| | NOTHING SHOWN FOR THIS? |
| | |
| | 13)NOTE: PLEASE NOTE MISSING EGRESS |
| | LIGHTING PER 210-70. PLEASE NOTE MANY |
| | UNITS COMING INTO FOYER HAVE A FIXTURE/ |
| | AND SOME DO NOT. PLEASE NOTE ANY OTHER |
| | LOCATIONS ON PLANS. SOME MISSING IN |
| | HALLWAYS AND /OR HABITABLE ROOMS. |
| | |
| | 14)NOTE: PLEASE NOTE SOME PAGES/NOTES |
| | REFERENCE OTHER PAGES AND THAT INFORMAT- |
| | -ION IS NOT SHOWN. PLEASE GO OVER PLANS. |
| | E1.29ETC/ |
| | |
| | 15)NOTE: PLEASE NOTE OTHERS SHEETS/UNITS |
| | SHOWING TWO PANEL AND APPEAR TO BE |
| | A DOUBLE PRINT? |
| | |
| | 16)NOTE:PLEASE NOTE MISSING OUTLET FOR |
| | A/C EQUIPMENT. PER 210-63 AND/OR SECTION |
| | 306 OF THE MECHANICAL CODE. |
| | ROOF TOP. |
| | |
| | 17)NOTE: PLEASE NOTE MISSING ELECTRICAL |
| | FOR ROOF TOP POOL/ POOL AREA /CABANAS?? |
| | |
| | 18)NOTE: PLEASE NOTE THAT SOME UNITS |
| | DO SHOW A/C UNIT CIRCUIT #`S ON PLANS |
| | BUT DO NOT CORRELATE WITH PANEL SCHEDULE |
| | (S). OTHER UNITS DO NOT SHOW ANY CIRCUIT |
| | #`S AT ALL. PLEASE SHOW . |
| | PLEASE NOTE SIZING OF OCP FOR AHU`S PER |
| | 424-3B. PLEASE NOTE THAT KW RATINGS THAT |
| | ARE SHOWN DO NOT SEEM BE COMMON SIZE?? |
| | |
| | 19)NOTE: PLEASE NOTE METER CENTER(S) IS |
| | SHOWING TYP AS 600A AND SOME ARE SHOWN |
| | AS 800A? PLEASE CORRELATE AND CLARIFY. |
| | |
| | 20)NOTE: PLEASE NOTE THAT THERE ARE SOME |
| | PANEL SCHEDULES SHOWNON SHEETS ARE NOT |
| | SHOWN ON RISER DIAGRAM.?? PLEASE SHOW. |
| | |
| | 21)NOTE: PLEASE NOTE NO OCP / WIRE / |
| | CONDUIT SIZES SHOWN FOR FIRE PUMP. |
| | 659-3,695-4,695-5 |
| | |
| | 22)NOTE: MISSING FEEDERS AND CONDUIT |
| | SIZES FOR MSB/ESB ,,,,,, |
| | |
| | 23)NOTE: PLEASE NOTE NO GFI PROTECTION |
| | SHOWN FOR ANY OF THE 277V/480V SERVICES |
| | RATED FOR MORETHAN 1000AMPS. |
| | 240-13/230-95 |
| | |
| | 24)NOTE: PLEASE NOTE ESB SHOWN AS 1600A |
| | ON RISER AND 1200A ON PNAEL SCHEDULE. |
| | PLEASE CORRELATE. |
| | |
| | 25)NOTE: PLEASE NOTE MCN AND MCS ARE |
| | SHOWN AS 4000A AND MCS SHOWN AS 5000A |
| | ON SCHEDULE? PLEASE CORRELATE. |
| | |
| | 26)NOTE: PLEASE SHOW ALL CONTINUOUS AT |
| | 125%. (LIGHTING ETC) |
| | 215-2,215-3,230-42 |
| | |
| | 27)NOTE: PLEASE SHOW GROUNDING ELECTRODE |
| | GOING TO BUILDING STEEL AND COLD WATER |
| | PER 250-50. SIZE PER 250-66 |
| | PLEASE NOTE THAT THERE IS NO GROUNDING |
| | DETAIL SHOWN. |
| | |
| | 28)NOTE: PLEASE LIST THE REQ`D ARC |
| | FAULT PROTECTED CIRCUITS ON PANEL |
| | SCHEDULES. PER 210-12 |
| | |
| | 29)NOTE: PLEASE NOTE THAT THE LOAD |
| | CALCULATIONS NEED TO BE SHOWN. SQ FT/ |
| | RECEPT LOADS ETC. PER 220-3,220-10, |
| | 220-11, 220-13. (215-5) |
| | PLEASE NOTE THAT NO LOAD CALCULATIONS |
| | ARE SHOWN FOR HOUSE SERVICES. PLEASE |
| | SHOW. |
| | |
| | 30) NOTE: PLEASE NOTE THAT ELECTRICAL |
| | SPEC BOOKS NEED TO BE SUBMITTED FOR |
| | REVIEW. |
| | |
| | 31)NOTE: PLEASE NOTE PER LOCAL AMENDMENT |
| | -S. COLOR CODING OF FEEDERS NEED TO BE |
| | NOTED ON PLANS. PLEASE NOTE THAT THE |
| | LOCAL AMENDMENTS ARE SHOWN IN THE AMEND |
| | BOOKS THAT WERE HANDED OUT IN THE PRE- |
| | PLAN REVIEW MEETING. |
| | |
| | 32)NOTE: PLEASE NOTE THAT ON E4.02, |
| | NOTE 19 SAYS "NOT USED", BUT IS # ON |
| | ELECTRICAL RISER DIAGRAM.?? |
| | |
| | PLEASE COMPLETE PLANS AND SUBMIT ALL OF |
| | THE ABOVE INFORMATION FOR REVIEW. IF |
| | THERE ARE ANY QUESTIONS, PLEASE CALL. |
| | |