Plan Review Notes
Plan Review Notes For Permit 02040434
Permit Number 02040434
Review Stop B
Sequence Number 2
Notes
Date Text
2002-06-21 00:00:00BUILDING DENIED
  
 1) THE OWNER/AGENT IS REQUIRED TO SIGN
 THE ENERGY CALC. FORM. AN ADDITIONAL
 COPY IS REQUIRED.
  
 2) PROVIDE DETAILS FOR THE ATTACHMENT OF
 THE WINDOW AND DOOR BUCKS TO THE
 STRUCTURE. INDICATE THE FASTENER TYPE,
 SIZE, SPACING AND EMBEDMENT. PER FBC
 SEC. 1707.4.4.2
  
 3) INDICATE ON THE PLANS THAT TERMITE
 PROTECTION WILL BE PROVIDED PER FBC
 SEC. 1816.
  
 4) THE WOOD USED FOR THE SCREENED PORCH
 SHALL BE APPROVED PRESERVATIVE TREATED
 WOOD SUITABLE FOR GROUND CONTACT. SEE
 FBC SECTION 2304. PLEASE INDCATE ON THE
 PLANS.
  
 5) THE STRUCTURAL ENGINEER WHOSE TITLE
 BLOCK IS ON SHEET 3 IS REQUIRED TO SIGN
 AND SEAL THE STRUCTURAL PAGES OF THE
 PLANS.
  
 6) PLEASE CLARIFY NOTE # 8 ON SHEET 3.
 THE INTERNAL PRESSURE COEFFICIENTS,GCPI
 FOR AN ENCLOSED BUILDING USING THE
 SIMPLIFIED METHOD IS + 0.18 AND - 0.18.
  
 7) NOTE #9 ON SHEET 3, STATES THAT THE
 OPENINGS ARE TO BE IMPACT RESISTANT.
 PLEASE CLARIFY. THE PRODUCT APPROVALS
 SUBMITTED INDICATE NON-IMPACT RESISTANT
 GLAZING AND STORM PANELS.
  
 8) PROVIDE A KEY PLAN AND INSTALLATION
 SCHEDULE FOR STORM PANELS (2 COPIES)
  
 9)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - SINGLE HUNG WINDOW
 - EXTERIOR INSWING DOOR AT UTILITY ROOM
  
 10) THE POSITIVE OPENING PRESSURE LISTED
 ON THE PLANS EXCEEDS THE POSITIVE DESIGN
 PRESSURE IN THE PRODUCT APPROVAL FOR THE
 AWNING WINDOWS. (PLAN HAS +38.3 AND THE
 PRODUCT APPROVAL IS RATED FOR +36.7)
  
 11) THE GLASS BLOCK OPENINGS WHICH ARE
 BOTH IN HAZARDOUS LOCATIONS ARE REQUIRED
 TO HAVE A MINIMUM FACE THICKNESS OF 0.25
 INCH.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202